The electrical connection must be performed dry, in a sealed
connection box whose cable glands must be tightened in order
to avoid any water infiltration.

4. Cable Cross-Section

CROSS-SECTION (mm²)

1,5

2,5

4

6

The voltage drop in the supply cable of the
Mini Brio M12 (&12K, 12B) & 12HW ca-
ble  should  be  limited  in  order  to  comply
with  the  applicable  standards  and  ensure
optimal illumination.

Follow  the  table  opposite  (one  projector
per cable);

Max. length
(m)

16 (M12)

26.7 (M12) 42.7 (M12)

64 (M12)

5. Projector Protection

Independent protection is necessary for each Mini Brio M12 (&12K, 12B) & 12HW. Protection must be ensured in the secondary
of the transformer using fuses or breakers at 2A or 3A.

A. Declaration of conformity

Bleu Electrique SAS (FR47403521693) declares that product  Mini Brio M12 (&12K, 12B) & 12HW is com-

pliant with the safety and electromagnetic compatibility requirements of European directives  E.M.C (2014/30/

UE), Low voltage (2014/35/UE), RoHS (2011/65/UE), WEEE (2002/96/CE) and REACH (1907/2006).