7. Projector Protection

Independent protection is necessary for each WEX30. Protection must be ensured in the secondary of the
transformer using fuses or breakers at 4A.

8. Cable section

SECTION (mm²)

2.5

4

6

10

The drop in voltage in the power supply cable of the WEX30
must be limited so that the colours are not altered.

Respect the table opposite (one projector per cable);

Max. length (m) 10.0

17.0

25.6

42.6

A. Connection schematic

B. Declaration of conformity

Bleu Electrique SAS (FR47403521693) declares that product WEX30 is compliant with the safety

and electromagnetic compatibility requirements of European directives 2006/95/CE and 2004/108/CE.

Emmanuel Baret

Marseilles, on 15/03/2017

Distributor's stamp

Date of sale: . . . . . . . . . . . . . . . . . . . . . . . Batch N°: . . . . . . . . . . . . . . . . . . . . . . . . . . .

www.c-

cei.fr

4

Summary of Contents for WEX30

Page 1: ...eatures Sizes Standard PAR 56 Installation In standard PAR 56 niche Power supply 12 V AC 50Hz 60Hz Power consumed 40W maximum according to colour LED type 9 powerful monochrome LEDs 3R 3G 3B 6 MidPower cool white LEDs 6000 K Risk group 1 low risk according to IEC62471 2006 Protection index IP 68 after installation Max luminous flux According to colour 1150 lm maxi white Color control RC RC BT or b...

Page 2: ...programmes with shorts cutting power supply Change of mode A small cut of power supply less than 1s switches to the next colour sequence Once all the colours are displayed the light goes back to the first colour pure white A cut of supply 2s resets the light synchronization and switches them to second colour blue After a long stop more than 4s the lights show the last displayed colour Fixed colour...

Page 3: ...he power upstream before handling the electrical instal lation Risk of electric shock Only connect to a circuit which is protected by a ground fault circuit interrupter If you are not sure if these types of devices are fitted contact a qualified electrician A standard PAR56 niche B PAR56 bulb support C Seal to crush during light installation This guarantees the tightness of the electrical connecti...

Page 4: ...e of the WEX30 must be limited so that the colours are not altered Respect the table opposite one projector per cable Max length m 10 0 17 0 25 6 42 6 A Connection schematic B Declaration of conformity Bleu Electrique SAS FR47403521693 declares that product WEX30 is compliant with the safety and electromagnetic compatibility requirements of European directives 2006 95 CE and 2004 108 CE Emmanuel B...

Reviews: