7. Projector Protection
Independent protection is necessary for each WEX30. Protection must be ensured in the secondary of the
transformer using fuses or breakers at 4A.
8. Cable section
SECTION (mm²)
2.5
4
6
10
The drop in voltage in the power supply cable of the WEX30
must be limited so that the colours are not altered.
Respect the table opposite (one projector per cable);
Max. length (m) 10.0
17.0
25.6
42.6