24
CD3000S
1PH from 10A to 90A
User’s manual
Firing Setting
8.1 Firing Setting with Analog Input Option
The BF firing performed in Digital mode in the Thyristor unit give a lot of advantages because switches Thyristor
at zero voltage crossing (ZC) without EMC interferences. Analog input is necessary for BF and can be decided
how many complete Cycle we want at 50% of power demand.
This value can be 4, 8 or 16 complete Cycles.
8
JP1
JP
6
JP
2
JP2
JP3
JP6
G1
K1
K2
G2
JP1
JP
3
JP4
CN1
CN2
+
+
+
+
+
-
+
-
JP5
JP4
JP5
K1
K2
G2
JP4
35A-45A
60A-90A
JP5
Firing Type
JP4
JP5
BF4
Open
Open
BF8
Close
Open
BF16
Open
Close
Summary of Contents for CD3000S-1PH series
Page 2: ......