30
REVEX
2PH from 120A to 210A
User’s manual
9.4.2 Setup Menu
This section describes each item on the setup menu. Use this menu to configure the power controller for the
load.
The password to access this menu is 2.
Parameter Name
Description
Range
Unit
Modbus
Address
Par.
Type
Out Scale
Set the percentage by which the set point
is scaled. For example, if a 0 to 10V analog
input providing the set point is 5V and output
scaling is 80% then the effective set point is
40%
0 to 100.0
%
16
Read
Write
Parameter Name
Description
Default
Range
Unit
Modbus
Address
Par.
Type
Nom Line V
Set the nominal value for the line
voltage input
220V
0 to 1023
V
37
Read
Write
Nominal I
Set the nominal load current
Maximum
current
0 to 999.9
A
38
Read
Write
SP select
Choose the source for the remote set
point
0
61
Read
Write
Option
Value
Analog In 1
0
Analog In 2
1
100
80
60
40
20
0
0 20 40 60 80 100
Input
Output Scaling = 100%
Output Scaling = 80%
Output Scaling = 40%
Scaled Set P
oint
Summary of Contents for REVEX 2PH 120A
Page 2: ......