REVEX
2PH from 120A to 210A
User’s manual
31
9.4.3 Advanced Setup Menu
This section describes each item on the advanced setup menu. Use this menu to configure the power
switching, closed loop control of power and adjustable settings for data logging and heater bakeout.
The
password to access this menu is 10.
Parameter Name
Description
Default
Modbus
Address
Par.
Type
Firing Type
Choose the firing mode
3
18
Read
Write
Option
Value
Zero Cross
1
Burst fire
3
DEFAULT:
Burst Fire
3
Parameter Name
Description
Default
Range
Unit
Modbus
Address
Par.
Type
Min Cycles
Set the minimum number of On
cycles and off cycles for burst firing
8
0 to 999.9
n°
20
Read
Write
Cycle time
Set the duration of one on-off cycle in
increments of 50mSec.
Applies to zero crossing
60
(3 sec)
0 to 255
0 to 12,75
sec)
24
Read
Write
Feedback
Choose the feed-back type
1
19
Read
Write
Option
Description
Value
V²
Voltage squared
0
None
No feed-back
1
I²
Current squared
2
Voltage
Voltage
32
Current
Current
64
Power
Power
128
External
External signal via analog input 2
256
DEFAULT:
None
1