32
REVEX
2PH from 120A to 210A
User’s manual
Parameter Name
Description
Default
Range
Unit
Modbus
Address
Par.
Type
Pb Power
Set the gain for the main loop. A larger
value yields a larger adjustment for a
given deviation
10%
0 to 255
%
26
Read
Write
Ti Power
Set how aggressively the integral part
of the control algorithm acts. A larger
settings yields a larger adjustment for
a given deviation over a given time
50
0 to 255
27
Read
Write
HB Sense
Set the threshold of resistance that
activates the Heater Break alarm. This
setting is in percentage of the nominal
load resistance
100%
0 to 100.0
%
29
Read
Write
HB Delay
Set a delay between when the
resistance drops below the value set
for a heater break sensitivity and when
the heater break alarm is indicated.
This set increments of 50mSec
50 (2,5
sec)
0 to 255
(0 to 12,75
sec)
28
Read
Write
Summary of Contents for REVEX 2PH 120A
Page 2: ......