REVEX
2PH from 120A to 210A
User’s manual
35
Parameter Name
Description
Default
Modbus
Address
Par.
Type
Alm Out Fn
Choose for which conditions the digital output
indicates alarm. The output always indicate an
alarm when the heat sink is over temperature. The
digital output is energized for normal operating
condition and de-energized when the power
controller is off or when there is an alarm.
Note!:
The power controller monitors for heater
break or short circuit condition only when included
in the option selected for Alarm Output Function
1
34
Read
Write
Option
Description
Bit
Heater Break
Heater Break
0
Short Circuit
Short circuit
1
Therm
SCR is over temperature
3
Communication
Communication watchdog error
4
DEFAULT
None
Alarm Bitwise is allowed
Parameter Name
Description
Default
Modbus
Address
Par.
Type
Start Disp
Choose which parameter is displayed on the home
page at power-up
1
60
Read
Write
Option
Value
Current
0
Volts Out
1
Power
2
DEFAULT:
Voltage
1
Summary of Contents for REVEX 2PH 120A
Page 2: ......