The Thyristor unit could be susceptible to interferences lost by near equipments or by the power supply, for
this reason in accord to the fundamental practices rules is opportune take some precautions:
• The coil contactor, the relays and other inductive loads must be equipped with opportune RC filter.
• Use shielded bipolar cables for all the input and output signals.
• The signal cables must not be near and parallel to the power cables.
• Local regulations regarding electrical installation should be rigidly observed.
Use copper cables and wires rated for use at 90°C only.
Power cable torque (suggested)
Type
Connector
Type
Torque Lb-in
(N-m)
Wire Range
mm²(AWG )
MAX Current
Terminals
Wire Terminals
UL Listed
(ZMVV)
030
035
040
Screw M5
26.6 (3.0)
1.5-10 (16-8)
50A
Rigid / Flexible
Spade Terminal
Cable dimensions of the Command Terminals
0.5 mm² (AWG 18)
Cable dimensions of the Earth (suggested)
6 mm² (AWG 10)