background image

REVO S 

1PH from 30A to 40A

 

User’s manual

17

External Fuse (not included)

The thyristor unit without IFH option (Internal Fuse + Fuse-Holder), must be protected by fuses against short circuit.
The Fuses must have I²t 20% less than thyristor’s I²t. The warranty of thyristor is null if no proper fuses are used.

Type

Fuse + Fuse-Holder 

Order Code

Fuse Code
Spare Part

Current

(ARMS)

I²T at 500Vac*

(A² sec.)

Vac

030

FFH1451/40A

FU1451/40A

40

525

660

035

FFH1451/50A

FU1451/50A

50

1260

660

040

FFH1451/50A

FU1451/50A

50

1260

660

 

*

 I2T are multiplied for K value in function of Vac at 500V K is 

equal to 0,7 (750 X 0,7 = 525    1800 X 0,7 =1250).        
At 660Vsc K is equal to 1.  

1.4

1.2

1.0
0.9
0.8
0.7

0.6

0.5

0.4

0.3

200        300          400         500         600          700

V

AC

K

Caution: 

High speed fuses are used only for the thyristor protection and can not be used to 

protect the installation.

Caution: 

The warranty of thyristor is null if no proper fuses are used. See table.

7

Summary of Contents for Revo C 1Ph 30A

Page 1: ...ev 10 2018 1PH Solid State Relay From 30 to 40A 002 M RS1 30 40 CD Automation S r l Via Picasso 34 36 20025 Legnano MI Italy Tel 39 0331 577479 Fax 39 0331 579479 E mail info cdautomation com Web www cdautomation com ...

Page 2: ......

Page 3: ...HE STANDARD Electrical safety Standard EN60947 1 2007 A1 2011 A2 2014 EN60947 4 3 2014 Generic Emission standard EN60947 4 3 2014 Group 1 Class A emissions Generic Immunity standard EN60947 4 3 2014 Industrial Immunity SODDISFA I REQUISITI DELLA NORMA Specifica di sicurezza EN60947 1 2007 A1 2011 A2 2014 EN60947 4 3 2014 Specifica sulle emissioni EN60947 4 3 2014 gruppo 1 emissioni classe A Specif...

Page 4: ...l Control Switches and equivalent to CSA C22 2 14 For more detail search for File E231578 on www ul com ESD Sensitive product use proper grounding and handling techniques when installing or servicing product Do not throw in trash use proper recycling techniques or consult manufacturer for proper disposal A NOTE marks a short message to alert you to an important detail A CAUTION safety alert appear...

Page 5: ...de puissance est de IP20 lorsque les couvercles sont installés et fermés L appareil doit être installé dans une enceinte qui assure toute la protection supplémentaire nécessaire pour l environnement et l application WARNING Ground the power controller via the provided protective earth grounding terminal Verify ground is within impedance specifications This should be verified periodically AVERTISSE...

Page 6: ...ectrostatique appropriées CAUTION Install an appropriately sized RC filter across contactor coils relays and other inductive loads ATTENTION Installer un filtre RC de dimensions appropriées sur les bobines du contacteur les relais et autres charges par induction NOTE Provide a local disconnect to isolate the power controller for servicing REMARQUE Fournir une déconnexion locale afin d isoler le ré...

Page 7: ...orization RMA Customers wishing to return any items whether they are incorrectly supplied faulty or damaged in transit must first complete a Return Material Authorisation RMA form to obtain an RMA number from the Service Department A full repair service is available for customers Prior to submitting the RMA form and returning products customers are recommended to contact the technical support team...

Page 8: ...al features 11 Input features 11 Output features power device 11 Environmental installation conditions 12 Derating Curve 12 Installation 13 Dimensions and Fixing holes 13 Wiring instructions 14 Connection Diagram for Single phase 15 Firing type 16 Zero Crossing 16 External Fuse not included 17 External Fuse holder Dimension not included 18 Trouble shooting 19 1 2 3 4 5 6 7 8 Summary ...

Page 9: ...e phase wiring with resistive load V Nominal voltage of the load I Nominal current of the load P Nominal power of the load Open Delta wiring with resistive load V Nominal voltage of the load I Nominal current of the load P Nominal power of the load I P V I P 3V 1 V V ...

Page 10: ...de Zero Crossing ZC Z Burst Firing 4 Cycles On at 50 Power Demand 4 Burst Firing 8 Cycles On at 50 Power Demand 8 Burst Firing 16 Cycles On at 50 Power Demand 6 CONTROL MODE 11 description code Open Loop 0 FUSES OPTION 12 description code No Fuse 0 Fuse Fuse Holder F Fuse Fuse Holder CT Y Fuse Fuse Holder CT HB H Fuse Fuse Holder CT HB with Flat Cable Connection X FAN VOLTAGE 13 description code N...

Page 11: ... device Nominal current in continuous service See order code Max peak current 10ms 360A for unit type 030 540A for unit type 035 700A for unit type 040 Nominal Voltage range Ue 24 600V Repetitive peak reverse voltage Uimp 1200V 480V 1600V 600V Latching current 250mA Leakage current 15mA eff FUSE I T value suggested at 500Vac tp 10msec 525 A s for unit type 030 1260 A s for unit type 035 1260 A s f...

Page 12: ...C 32 104 F at nominal current Over 40 C use the derating curve Storage temperature 25 C to 70 C 13 F to 158 F Installation place Don t install at direct sun light where there are conductive dust corrosive gas vibration or water and also in salty environmental Altitude Up to 1000 meter over sea level For higher altitude reduce the nominal current of 2 for each 100m over 1000m Humidity From 5 to 95 ...

Page 13: ... Thyristor unit must be always mounted in vertical position to improve air cooling on heat sink Maintain the minimum distances in vertical and in horizontal as represented When more unit has mounted inside the cabinet maintain the air circulation like represented in figure Sometimes is necessary installing a fan to have better air circulation Dimensions and Fixing holes 5 cm 15 cm 2 cm AIR AIR 4 3...

Page 14: ... bipolar cables for all the input and output signals The signal cables must not be near and parallel to the power cables Local regulations regarding electrical installation should be rigidly observed Use copper cables and wires rated for use at 90 C only Power cable torque suggested Type Connector Type Torque Lb in N m Wire Range mm AWG MAX Current Terminals Wire Terminals UL Listed ZMVV 030 035 0...

Page 15: ...nsure that the unit can be electrically isolated from the supply this allows the qualified people to work in safety 2 The thyristor unit must be protected by extrarapid fuses optional The Fuses must have I t 20 less than thyristor s I t The warranty of thyristor is null if no proper fuses are used see technical data 3 The heat sink must be connected to the earth ...

Page 16: ...rs and the Thyristor operates like a contactor The Cycle time is performed by temperature controller ZC minimizes interferences because the Thyristor unit switches ON OFF at zero voltage Led status and Alarms LED STATUS DESCRIPTION ON Load is NOT powered Load is powered OFF ON Voltage Supply V Load Voltage V SSR from controller ON OFF 6 ...

Page 17: ... Current ARMS I T at 500Vac A sec Vac 030 FFH1451 40A FU1451 40A 40 525 660 035 FFH1451 50A FU1451 50A 50 1260 660 040 FFH1451 50A FU1451 50A 50 1260 660 I2T are multiplied for K value in function of Vac at 500V K is equal to 0 7 750 X 0 7 525 1800 X 0 7 1250 At 660Vsc K is equal to 1 1 4 1 2 1 0 0 9 0 8 0 7 0 6 0 5 0 4 0 3 200 300 400 500 600 700 VAC K Caution High speed fuses are used only for t...

Page 18: ...18 REVO S 1PH from 30A to 40A User s manual 117 5 112 43 70 36 45 0 5 External Fuse holder Dimension not included ...

Page 19: ...s of the symptom Actions Load current doesn t flow Green LED ON light OFF No input signal Reversed polarities of input signal Give input signal Reverse the input signal polarity Green LED ON light ON No voltage power Fuse failure Load failure Thyristor failure Check the wiring Change the fuse Check the load Change the module Load current flow also without input signal Green LED ON always light OFF...

Page 20: ...CD Automation S r l Via Picasso 34 36 20025 Legnano MI Italy Tel 39 0331 577479 Fax 39 0331 579479 E mail info cdautomation com Web www cdautomation com ...

Reviews: