Current
Power Supply Cable
Load Cable (Output)
Earth
mm²
AWG
mm²
AWG
mm²
AWG
25A (S09)
10
8
10
8
4
12
35A (S09)
10
8
10
8
6
10
45A (S09)
10
8
10
8
6
10
75A (S09)
25
4
25
4
10
8
100A (S11)
35
3
35
3
16
6
125A (S11)
50
1
50
1
16
6
150A (S11)
70
1/0
70
1/0
16
6
225A (S13)
120
4/0
120
4/0
25
4
300A (S14)
2 x 70
2 x 1/0
2 x 70
2 x 1/0
50
1
350A (S14)
2 x 95
2 x 3/0
2 x 95
2 x 3/0
50
1
400A (S14)
2 x 95
2 x 3/0
2 x 95
2 x 3/0
50
1
450A (S14)
Bus Bar 30 x 6 mm
Bus Bar 30 x 6 mm
70
1/0
500A (S14)
Bus Bar 60 x 4 mm
Bus Bar 60 x 4 mm
70
1/0
600A (S14)
Bus Bar 60 x 4 mm
Bus Bar 60 x 4 mm
70
1/0
7.1.3
Cable dimensions of the Command Terminals
Maximum connection capacity for all size: 1.5 mm2 (14 AWG)