CD Automation srl
REVO E-3PH from 25A to 500A
User’s Manual
31
10.2.2
Suggested recipe for Burst Firing
The firing type has already configured in line with customer requirements that are defined in the Order
Code. The Order Code is written on the identification label.
However, if you wish to change the firing type you can use the software configurator or the Control Panel
(see par. 0).
Caution:
this procedure must be performed only by qualified persons.
OPERATOR MENU
Parameter Name
Value
Description
UM
Mode
P003 (H03)
0
Setpoint selection Analog/Digital
R/W
P004 (H04)
Digital Setpoint value
%
R/W
P019 (H13)
100
Maximum Output
%
R/W
P024 (H18)
0
Setpoint Ramp Up
Sec
R/W
P025 (H19)
0
Setpoint Ramp Down
Sec
R/W
P116 (H74)
V Load
Operative load voltage
V
R/W
P119 (H77)
I Load
Load nominal current
A
R/W
SETUP MENU
Parameter Name
Value
Description
UM
Mode
P023 (H17)
0
Firing Type
R/W
P066 (H42)
20
HB sensitivity
%
R/W
P070 (H46)
1
Feed back selection
R/W
P083 (H53)
8
Burst Firing Cycles (Not used in Phase Angle)
Cycles R/W
P084 (H54)
<P083
² Ramp Cycles of Burst (Not used in Phase Angle)
Cycles R/W
P085 (H55)
0
Delay triggering
°
R/W
P090 (H5A)
1
Limit current Analog/Digital
R/W
P091 (H5B)
0÷
Digital Limit current value
%
R/W
P098 (H62)
0÷3
Define the load type connection:
0=star
1=star+N
2=delta
3=open delta
R/W
= modification is not necessary
= modification is necessary
If the current limit is not used set this value to 100,0%.