REVO S
3PH from 300A to 800A
User’s manual
23
5.6 Control Terminals
Warning:
Before connecting or disconnecting the unit check that power and control cables
are isolated from voltage sources.
M1
Terminal
Description
1
NO - Normally Open contact alarm relay output (Thermal or SC/HB)
2
C - Common contact alarm relay output
3
NC - Normally Close contact alarm relay output (Thermal or SC/HB)
4
Not Connected
5
DI 2 - Enable Digital Input
6
DI 1 - Configurable Input
7
Not Connected
8
Not Connected
9
10Vdc stabilized 1 mA MAX
10
0V GND
Terminal
Description
11
- Analog Input 1 (0-10Vdc/4-20mA Analog Setpoint)
12
+ Analog Input 1 (0-10Vdc/4-20mA Analog Setpoint)
13
COM I - Common Digital Input
14
Not Connected
15
Fan supply (230V Standard - 115 Option - for DC Fan 24Vdc)
16
Fan supply (230V Standard - 115 Option - for DC Fan Option -24Vdc)
17
Not Connected
18
Aux – Voltage Supply for electronic boards and synchronization
(See order code for the Value)
19
Not Connected
20
Aux – Voltage Supply for electronic boards and synchronization
(See order code for the Value)
M2
Terminal
Description
1
24V Out Max 5mA
2
Slave Output
3
Not Connected
4
0V GND