background image

REVO SSR

 

User’s manual

9

Identification and Order Code

1.1 Identification of the unit

Caution:

 Before to install, make sure that the Thyristor unit have not damages. If the product 

has a fault, please contact the dealer from which you purchased the product.

CURRENT

4 5 6

description

code

62A

0 6 2

74A

0 7 4

90A

0 9 0

MAX VOLTAGE

7

description

code

480V

4

600V

6

VOLTAGE SUPPLY AUX

8

description

code

No Auxiliary Voltage supply

0

INPUT

9

description

code

SSR

S

FIRING

10

description

code

Zero Crossing ZC

Z

Random (for connection with REVO PC)

R

CONTROL MODE

11

description

code

Open Loop

0

FUSES & OPTION

12

description

code

No Fuse

0

FAN VOLTAGE

13

description

code

No Fan

0

APPROVALS

14

description

code

CE EMC For European Market

0

MANUAL

15

description

code

None 

0

Italian

1

English 

2

German 

3

French

4

VERSION

16

description

code

Std version

1

1

1.2 Order Code

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

REVO SSR

S

S

R

_

_

_

-

_

_

_

_

_

_

_

_

_

_

The identification label give all the information regarding the factory 

settings of the Thyristor unit, this label is on the unit, like represented 

in figure. Verify that the product is the same thing as ordered.

Summary of Contents for REVO SSR

Page 1: ...MANUAL Rev 02 2021 REVO SSR Solid State Relay 007 M RSSR CD Automation S r l Via Picasso 34 36 20025 Legnano MI Italy Tel 39 0331 577479 Fax 39 0331 579479 E mail info cdautomation com Web www cdautomation com ...

Page 2: ......

Page 3: ...fety Standard EN60947 1 2007 A1 2011 A2 2014 EN60947 4 3 2014 Generic Emission standard EN60947 4 3 2014 Group 1 Class A emissions Generic Immunity standard EN60947 4 3 2014 Industrial Immunity SODDISFA I REQUISITI DELLA NORMA Specifica di sicurezza EN60947 1 2007 A1 2011 A2 2014 EN60947 4 3 2014 Specifica sulle emissioni EN60947 4 3 2014 gruppo 1 emissioni classe A Specifica sulle Immunità EN6094...

Page 4: ...Switches and equivalent to CSA C22 2 14 For more detail search for File E231578 on www ul com ESD Sensitive product use proper grounding and handling techniques when installing or servicing product Do not throw in trash use proper recycling techniques or consult manufacturer for proper disposal A NOTE marks a short message to alert you to an important detail A CAUTION safety alert appears with inf...

Page 5: ... environment and application AVERTISSEMENT L indice de protection du régulateur de puissance est de IP20 lorsque les couvercles sont installés et fermés L appareil doit être installé dans une enceinte qui assure toute la protection supplémentaire nécessaire pour l environnement et l application WARNING Ground the power controller via the provided protective earth grounding terminal Verify ground i...

Page 6: ... thyristor units here described have been designed for use with sinusoidal networks with nominal frequency 50 60 Hz Any application with NON SINUSOIDAL distorted or disturbed networks could compromise the correct operation of the unit ATTENTION Les unités de thyristors décrites ici ont été conçues pour être utilisées avec des réseaux sinusoïdaux d une fréquence nominale de 50 à 60 Hz Toute applica...

Page 7: ... RMA Customers wishing to return any items whether they are incorrectly supplied faulty or damaged in transit must first complete a Return Material Authorisation RMA form to obtain an RMA number from the Service Department A full repair service is available for customers Prior to submitting the RMA form and returning products customers are recommended to contact the technical support team to deter...

Page 8: ... of the unit 9 1 2 Order Code 9 Technical Specifications 10 2 1 General features 10 2 2 Input features 10 2 3 Output features power device 10 2 4 Environmental installation conditions 10 2 5 Dissipation Curves 11 Installation 12 3 1 Dimensions and Fixing holes 12 Wiring instructions 13 4 1 Connection Diagram 13 Trouble shooting 14 1 2 3 4 5 Summary ...

Page 9: ...iption code Zero Crossing ZC Z Random for connection with REVO PC R CONTROL MODE 11 description code Open Loop 0 FUSES OPTION 12 description code No Fuse 0 FAN VOLTAGE 13 description code No Fan 0 APPROVALS 14 description code CE EMC For European Market 0 MANUAL 15 description code None 0 Italian 1 English 2 German 3 French 4 VERSION 16 description code Std version 1 1 1 2 Order Code 1 2 3 4 5 6 7...

Page 10: ...ng current 250mA Leakage current 15mA eff FUSE I T value suggested at 500Vac tp 10msec 525 A s for unit type 62 1260 A s for unit type 74 1260 A s for unit type 90 Frequency range 47 70Hz Power loss I Inom see the Dissipation Curves Isolation Voltage Ui 2500Vac 2 4 Environmental installation conditions Ambient temperature 0 40 C 32 104 F at nominal current Over 40 C use the derating curve max 50 C...

Page 11: ...T CAPABILITY 120 100 80 60 40 20 0 120 100 80 60 40 20 0 HEATSINK TYPE 0 25 50 75 100 125 Ambient Temperature C 5 C W 3 C W 2 C W 1 5 C W 1 C W 0 5 C W Power Lost Power Max Current allowed by terminals 0 20 40 60 80 90 I rm s Current A LOAD CURRENT CAPABILITY 140 120 100 80 60 40 20 0 Power Lost Power Max Current allowed by terminals 0 25 50 75 100 125 150 140 120 100 80 60 40 20 0 Ambient Tempera...

Page 12: ...lation The Thyristor unit must be used in conjunction with an appropriate heat sink Optional The heat sink must be sized in relation to environment temperature and the load current see the Dissipation Curves The assembly module heatsink must happen on a flat surface with low roughness The fixing holes on the heat sink must be threaded and countersunk Spread a layer of thermo conductive silicon put...

Page 13: ...upply for this reason in accord to the fundamental practices rules is opportune take some precautions The coil contactor the relays and other inductive loads must be equipped with opportune RC filter Use shielded bipolar cables for all the input and output signals The signal cables must not be near and parallel to the power cables Local regulations regarding electrical installation should be rigid...

Page 14: ...symptom Actions Load current doesn t flow Green LED ON light OFF No input signal Reversed polarities of input signal Give input signal Reverse the input signal polarity Green LED ON light ON No voltage power Fuse failure Load failure Thyristor failure Check the wiring Change the fuse Check the load Change the module Load current flow also without input signal Green LED ON always light OFF Wrong wi...

Page 15: ...CD Automation S r l Via Picasso 34 36 20025 Legnano MI Italy Tel 39 0331 577479 Fax 39 0331 579479 E mail info cdautomation com Web www cdautomation com ...

Reviews: