How to connect the starter
Caution:
this procedure must be performed only by qualified persons.
•
The control line supply ensuring that is OFF.
•
The power line supply ensuring is OFF.
•
The motor ensuring that its coupling correspond to the suppy voltage.
•
Select the cable sizing in accordance with instuctions of this manual.
•
Connect the starter in details power and control following the application diagram.
5.1
Wiring details
Use copper cables and wires rated for use at 75°C only.
5.1.1
Power cable torque (suggested)
STE Size
Connector
Type
Torque
Lb-in (N-m)
Wire
Range
AWG / kcmil
Wire
Terminal
SIZE 9
Terminal Block
M8
265 (30.0)
8
4/0
Copper wire
Compact (Solid) Stranded
SIZE 11
Bus Bar
with M8 screw
505 (57.0)
2
350
UL Listed (ZMVV)
Copper Tube Crimp. Lug
SIZE 13
Bus Bar
with M10 screw
505 (57.0)
1
600
UL Listed (ZMVV)
Copper Tube Crimp. Lug
SIZE 14
Bus Bar
with M10 screw
505 (57.0)
Bus Bar 30x6mm
Bus Bar 60x6mm
5.1.2
Power cable dimensions (suggested)
Current
Power Supply
Cable
Motor Cable
(Output)
Starter Bypass
(with Bypass)
Earth
mm² AWG mm² AWG mm² AWG mm² AWG
14A÷45A
10 8 10 8 10 8 6 10
50A÷76A
35 2 35 2 35 2 16 4
80A÷95A 50 1/0 50 1/0 50 1/0 25 2
100A÷112A
75 3/0 75 3/0 75 3/0 35 2
120A÷170A
95 4/0 95 4/0 95 4/0 50 1/0
190A÷225A
2 x 75
2 x 3/0
2 x 75
2 x 3/0
2 x 75
2 x 3/0
95
4/0
230A÷346A
Bus Bar 30 x 6 mm
Bus Bar 30 x 6 mm
Bus Bar 30 x 6 mm
2 x 75
2 x 3/0
398A÷450A
Bus Bar 60 x 5 mm
Bus Bar 60 x 5 mm
Bus Bar 60 x 5 mm
Bus Bar 30 x 6 mm
500A÷865A
Bus Bar 60 x 6 mm
Bus Bar 60 x 6 mm
Bus Bar 60 x 6 mm
Bus Bar 30 x 6 mm
5.1.3
Cable dimensions of the Command Terminals
Maximum connection capacity for all size: 1.5 mm2 (14 AWG)