Page
CDK Electronics Ltd, 17/19, Buxton Road, Congleton, Cheshire. CW12 2DW.
Tel 01260 296300. Fax 01260 296301.
www.cdk.co.uk
6
DC68K Pack Contr
oller
- I
ssue 1.
1a
- Sept 2001
SYSTEM
BACKUP
&
FAILURE
MODES.
If the DC68K is connected to a Storescan III system, a copy of the configuration is held
within the Storescan, this enables the control settings to be adjusted from the Storescan,
and the settings to be backed up. However it is important to note that the Storescan must
be put into program mode before any adjustments are made within the DC68K. Failure to
do so will mean that the Storescan will restore the original settings the next time they
communicate.
Note:
Setting adjustments must be accepted at the Storescan or the original settings will
be restored.
If communications between the DC86K and PACK-IO’s are lost, then a four and a half
minute timer is started and during this period no stages are turned off or on. If
communications have not been re-established before this timer has elapsed, then all stages
will drop out allowing the mechanical backup to take control. At this point the alarm relay
on the PACK-IO will drop out.
If power is lost to a PACK-IO then all stages will drop out, allowing the mechanical
backup to take control. At this point the alarm relay on the PACK-IO will also drop out.
Summary of Contents for DC68K