16: EPO Logic setting
Interface
Setting
Parameter 2:
Set up the EPO function control logic.
AO:
Active Open (Default). When AO is selected as EPO
logic, it will activate EPO function with Pin 1 and Pin 2 in
open status.
AC:
Active Close. When AC is selected as EPO logic, it will
activate EPO function with Pin 1 and Pin 2 in close status.
17: External output isolation transformer connection
Interface
Setting
Parameter 2:
Allow or disallow external output isolation
transformer connection.
ENA:
If selected, it’s allowed to connect to an external
output isolation transformer.
DIS:
If selected, it’s not allowed to connect to external
output isolation transformer. (Default)
18: Display setting for autonomytime
Interface
Setting
Parameter 2:
Set up the display setting for autonomy time
EAT:
If EAT is selected, it will display the remaining
autonomy time. (Default)
RAT:
If RAT is selected, it will show accumulated autonomy
time so far.