19: Acceptable input voltaje range setting
Interface
Setting
Parameter 2:
Set the acceptable high voltage point and
acceptable low voltage point for input voltage range by
pressing the Down key or Up key.
HLS:
Input high voltage point
For 200/208/220/230/240 VAC models:
280/290/300:
setting the high voltage point in parameter
2. (Default: 300Vac)
For 100/110/115/120/127 VAC models:
140/145/152:
setting the high voltage point in parameter
2. (Default: 150Vac)
LLS:
Bypass low voltage point
For 200/208/220/230/240 VAC models:
110/120/130/140/150/160:
setting the low voltage
point in parameter 2. (Default: 110Vac)
For 100/110/115/120/127 VAC models:
50/60/65/70/75/80:
setting the low voltage point in
parameter 2.(Default: 55Vac)
00: Exit setting
Interface
Setting
Exit the setting mode.
3.6.Operating Mode Description
Operating Mode
Description
LCD Display
Online mode
When the input voltage is within
acceptable range, UPS will provide
pure and stable AC power to output.
The UPS will also charge the battery
at online mode.