background image

365

UPO33

23<<

>>24

4. "Up Arrow" and "Down Arrow": Used to change the options in the sub-menus on 

the LCD. 

5. "Enter / Esc": Allows you to enter or exit a sub-menu in the LCD. It also serves to 

turn the siren on the UPS by a small amount of time.

6.LED Out: Indicates whether the output voltage of UPS or any problems with the 

output. 

7.LED investor: Indicates the status of the investor. When the inverter is switch-on 

is green. If off is red.

8.LED Battery: Indicates the battery status. If the batteries are functioning normally 

be green and if a problem will be red. 

9.LED 's BYPASS: When the UPS is in bypass mail the four LEDs light up intermit

-

tently.

10.LED Rectifier: Indicates the status of the charger. 

11.LED Network: Whether there is any abnormality to the UPS input. When the 

input is normal is green when there is a problem in red. 

12. "OFF": You can take the UPS.

The following table gives a more detailed description of the meaning of the LEDs 

on the mimic.

Table 7.1 Meaning of the LEDs.

green;. out = green.

!

output load. however,the batteries are charging.

!

network 

= red;. charger = red. batteries = 

green;. inverter = green;. out = green.

!

there was an abnormal event at the entrance of ups and 
the  load is  being  fed through  the inverter, the  energy 
stored in batteries.

!

8J>UB?P

 = red;. charger = red;. batteries = flashing 

red-green. inverter = green;. out = green.

!

no energy input  and energy  in  the  batteries are running 
low. it  also  generates an  audible  alarm. the  display 
willshow  "low  battery alert". it  is advised  to  turn  off all 
computers that are connected to ups.

!

network = flashing red-green

!

the network is not optimal to switch to manual bypass.

!

8J>UB?P!i!$J::BU!!

no synchronization: the network 

conditions are 

close to be appropriate but are not required.

!

8J>UB?P!i!?J9!

the entry conditions are  not  suitable to  enter bypass, 
so this  operation is  not  allowed because  it could  raise 
problems with the load.

!

BD>!i!?J9!

the load is not being fed by the ups. consult service.

!

output = flashing red-green

!

the 

load is 

being 

supplied by 

the bypass, 

and the network conditions are not good.

!

BD>!i!<?JJ8!

the  load is  being  fed by  the ups through  the 
inverter or bypass still appropriate network conditions.

!

bypass leds, lighting intermittently

!

the electronic bypass is activated.

!

!

K"1"+'()>,.+6-0%,$'+50L<-

 

the ups has lights on the front that displays the status of ups as follows: 

• if the lights

 are blues means that the load is being fed through either the inverter or bypass. 

• if the lights

 are reds means that the load is being fed to the energy stored in batteries 

• if the lights

 are flashing red and blue is because the charger is not working properly. the cause may be who 

missed one or two phases to the entrance. 

•  when

 the  charger starts  and if  there  is  no problem, the  lights  are flashing blue and  violet. 

• if you

 used the emergency shutdown of the ups, the light has a violet color. 

 

K":"+'5&+0/<-$,(0%

 

figure 5.2 illustrates the operation of the lcd, and table 5.2 below gives a description of each display.

 

!

!

3;<D?J!S('(!3?B8>#:!A#8J:(

 

control panel parts

 

1. Epo: emergency power off button. when activated, the computer shuts down completely. 

2. "on": It transfer the UPS from total shutdown mode to bypass mode (Pressing it for  more than 6 seconds) 

and from bypass mode to normal operation mode (Pressing the button  for more than 1 second). 

3. Lcd: the lcd screen displays information about the operation of ups battery status, input voltages, alarms,etc. 

4. "Up Arrow" and "down arrow": used to change settings in the sub-menus on the lcd. 

5. "Enter / esc": allows you to enter or exit a sub-menu in the lcd. it also serves to silence the siren of the ups 

for a while. 

6. output led: indicates whether the output voltage of the ups, or if there is any problem with the output. 

7. inverter led: indicates the status of the inverter. when the inverter is on is green. if off is red. 

8. battery led: indicates the battery status. if the batteries are functioning normally be green and if a problem 

will be red. 

9. bypass led: when the ups is in electronic bypass,  the two leds light up intermittently. 

10. charger led: indicates the status of the charger. 

11. network led: indicates whether there is any abnormality at the ups input. when the input is normal, the led 

is  green color,  when there is a problem is red color. 

12. "off": It transfers the UPS from normal operation mode to bypass mode (Pressing it for about 3 seconds) 

and from bypass mode to total shutdown mode (Pressing the button for more than 6 seconds). 

 

the following table gives a more detailed description of the meaning of the leds on the mimic. 

 

!

/'4<!!E+/+&!

4'<E&#HE#X,!

network  = green. charger =  green;. batteries = 
green;. investor = green;. output = green.

!

the ups is operating normally

!

network = 

green;. charger = 

green;. batteries = flashing 

yellow-

orange. inverter = 

green;. out 

= green. 

!

the ups operates 

normally, but 

the 

batteries are 

charging. if  a power  failure the ups entry will  have  no 

autonomy,  because the  batteries  are  not charged to 

100%.

 

!

network = 
green;. charger = red. batteries = red. inverter = 

the  batteries are  completely  discharged, in  case  of 
a court there 

is 

no energy input to the 

Table 5.1. meaning of the leds.

Summary of Contents for UPO33

Page 1: ...ual Three PhaseUPS WithIntegratedMonitoringSystem CHICAGO DIGITAL POWER Chicago Digital Power Incorporated 1193 W Higgins Elle Groove Village Il 60007 Tel 847 718 9545 Fax 847 718 9546 www cdpups com 365 UPO33 ...

Page 2: ...r to implementation 6 OPERATING PROCEDURES 6 1 Comissioning 6 2 Total Shutdown 6 3 Normal to electronic bypass transference 6 4 Manual Bypass 6 5 Alarm Reset 7 OPERATION 7 1 Control Panel 7 2 Front cover lights 7 3 LCD operation 7 4 UPSmenudescription 27 7 5 Emergency shutdown 8 ALARMS 8 1 Active alarms 8 2 Alarm reset and UPS normalization 9 COMMUNICATIONS 9 1 RS 232 port 9 2 Net adapter Optional...

Page 3: ... upright Upon receipt of the check the packaging machine which must be in perfect condition no hits no breaks free from excessive moisture otherwise immediately notify the carrier and our company During storage of ups it must be placed in a suitable place where not exposed to direct sunlight or near heat sources such as boilers stoves etc As one should not store near water pipes or in wet envi ron...

Page 4: ... the fit of connectors Here are some safety recommendations during installation operation and maintenance of the UPS All work must be intervention at UPS Realize by qualified personnel Prior to installation of the equipment must verify that all breakers are in the OFF position mainly batteries and must be handled only when the UPS is completely interconnected to rush for strict compliance to the p...

Page 5: ...ver Lights Communication ports RS232 and RJ 45 optional Cooling slots Frontal Panel Lock Front cover lights Communications ports RS232 and RJ 45 optional Cooling Slots Transient supressor Dual Input bypass breaker Optional Input breaker Output breaker Manual bypass breaker Battery breaker Transient supressor Dual input bypass breaker Optional Input breaker Output breaker Manual bypass breaker Batt...

Page 6: ...KJ B 9 EB88JE J9 B KJ C 8 K BD K 8 J JE B8 E U EK V J9 B8 2 d 0KJ K BAJ B8 CB9J UKJ8 KJ J U BCJ B BF BTJ B 9 KJ BD AD KJ J U J J 89 VBTJ KJ 8BC 8 T DJ BF BAJ B8 B KJ V J VJ8EK BB CDEK 9 EK J9 1IFD 8 C 8D V A CB9J UKJ8 KJ B 9 EB88JE J9 9 JE B KJ C 8 K BD K V A E ED K J KJ G42 J F JC 8 D8J8J XJ9 0K CB9J BU KJ D J B BAJ B B E BD E J B GJ 1IFD 18 K BAJ B8 CB9J KJ B 9 EB88JE J9 B KJ C 8 K BD K 8 J JE B...

Page 7: ... inside the UPS is above the nominal value of operation or when the battery pack is deeply discharged In this state the load is powered from the network through the bypass breaker When the UPS is in manual bypass the load is supplied directly from the network through the bypass breaker while the UPS remains de energized This allows maintenance on the UPS without interrupting power to the load In f...

Page 8: ... the input of the UPS before the bat estuaries discharge 5 Press the OFF for five seconds 6 Press the ON for more than six seconds 7 See procedure in Section 6 4 8 See procedure in Section 6 4 9 See procedure in Section 6 2 10 See procedure in Section 6 1 11 Turn off the bypass breaker 12 Switch the bypass breaker 13 When it returns to the input energy and the batteries are discharged 14 See proce...

Page 9: ... 208 VAC There must be a unique breaker to the UPS distribution panel Each line entry and exit should have adequate thickness to withstand the current passing through it The current driving the UPS and hence the sizes of the wires at the entrance and exit agreements changes do to their ability as shown in the following tables FIGURE 4 1 UPS PACKAGING FIGURE 4 2 UPS ANCHORED TO THE PALLET 1 A79 ABC...

Page 10: ...itches are turned off Check that all loads are off Check the polarity of the battery bank h We recommend using a three phase industrial breaker GHEEBGFDHE FBA2DEIJ9 To access the terminals in the ups of 20 kva to 30 kva remove the back cover the terminals are at the bottom in the ups of 40 kva to 80 kva the terminals are located on the front face to access them you must first open the front cover ...

Page 11: ...ILURE and you will hear a beep If this is the case check that batteries are properly connected and the battery breaker is on If when installing the UPS was an error in the phases connection turning on the UPS on the screen appears an alarm FAILURE SEQUENCE BYPASS In this case the UPS will not operate in bypass mode but it will operate in normal mode of operation To solve the problem correctly conn...

Page 12: ...have the correct polarity Turn the output breaker At this point will begin to supply the load through the bypass Turn the manual bypass breaker For the UPS is operating in normal mode press the ON for more than a second It is recommended that the bypass breaker manipulation is done by quali fied personnel 6 5 Alarm Reset See section 8 2 The UPS UPO33 includes a control panel that displays the stat...

Page 13: ...he lights are reds means that the load is being fed to the energy stored in batteries if the lights are flashing red and blue is because the charger is not working properly the cause may be who missed one or two phases to the entrance when the charger starts and if there is no problem the lights are flashing blue and violet if you used the emergency shutdown of the ups the light has a violet color...

Page 14: ... batteries IF the lights are flashing red and blue is because the charger is not working properly The cause may be that missed one or two steps at the entrance When the charger starts and there is no problem if the lights are flashing blue and violet If you use the emergency shutdown of the UPS the light has a violet color 7 3 LCD operation In Figure 7 2 illustrates the operation of the LCD and in...

Page 15: ... all three phases and frequency Table 5 2 Description of the UPS menus 0 4 E H C 8 CJ8D This is the main menu display this screen shows the ups operating status in this case is in normal operation it also displays the web address of manufacturer date and time in this menu you can also update the date and time to make it do the following press three times the enter esc button and the last two digit...

Page 16: ...and the batteries are discharged the causes may be dc fuse open loss of any of the input phases input voltage phase neutral outside the operating range 80 to 150 volts rms check the input voltages call for service RECTIFIER TURN ON is on the battery charger 8 INVERTER TURN ON The invertir is turned on 8 MANUAL INV SHUTDOWN inverter has been turned off manually 8 EMERGENCY PWR OFF emergency shutdow...

Page 17: ...D the ups batteries are depleted one possible cause is that the ups has operated in battery mode for long wait for the ups input is normal and start charging the batteries if after the input is normal the battery will not charge call service DC FUSE BLOWN the dc fuse is open this happens when you turn the battery breaker before you turn on the charger when you are starting the ups support call 5 V...

Page 18: ...battery warning 8 CHECK FANS the blowholes are more than 5 years of use it is advisable to change the FANS to perform the operation contact technical support SELFDIAGNOSTIC alarm information indicates that event counters ups have flooded the memory limit note this does not imply a malfunction of the machine diagnostic is recommended by software call support PWR SUPPLY WARNING it is activated when ...

Page 19: ...ppears when you turn on the ups 8 TEMPERATURE ALERT this alarm occurs when there is a high temperature in the computer but not high enough to go to bypass check the temperature of where the ups is located check the air conditioning system because it may be a fault AMBIENT TEMP OK it is activated when the temperature is at an optimum level after having been high 8 START BATTERY TEST has been initia...

Page 20: ...inverter overflow of the investor check for shorts to the output verify that the load does not consume more power than it is capable of supplying the ups check the temperature of where the ups is located avoid charges that generate large surges in short time if the problem persists call service Ij4 3 Q G0 3 L the frequency of the input bypass is not adequate to power the loads wait until the frequ...

Page 21: ...nd using a USB to serial converter TRENDnet TU S9 Monitoring can be done from a PC using HyperTerminal which is included in Windows versions less than or equal to Windows XP For more recent versions can be down loaded from the Internet Give the connection a name and select an icon and click OK Then in the next window in the Connect using select the port where the UPS is connec ted and click OK see...

Page 22: ...1 4 Click on the button off and then Properties Then see the window shown in Figure 9 1 5 Select the Settings tab and click on the ASCII Setup see Figure 9 1 6 In the next window select the Add linefeed at the end of each line received and click OK to see the window in Figure 9 1 4 and click on the button call ...

Page 23: ...s Additionally provide the UPS MIB to adapt to an environment with a professional monitoring NMS program such as OpenView If allowed the UPS is able to send E MAIL s warning to 8 different email addresses in case of abnormal operating conditions including cell phone numbers The cellular modem allows a GSM network to monitor the UPS status This system allows real time knowledge of the behavior of e...

Page 24: ... normally closed switch thus complementary signals For example when the UPS inverter is operating normally the normally open switch is open and normally closed switch is closed If the inverter fails the normally open switch closes and the normally closed switch will open With the ability to customize the UPS is easy to adapt the UPS to the particular characteristics of virtually any power plant Th...

Page 25: ...oundingsystemgenerally verifyingthattheneutralofthetransformersecondaryoverallsystempowerisreferenced tothispoint Theinputandoutputconductorsmustberoutedtogethertoavoidfeedback andachieveelectromagneticcompatibility Itmustestablishthattheminimumdistancesofventilation maintenanceandoperationof theUPStothewallsorbarriersaround mustbeatleast500mm 50cm Theboardshouldhavearegulatedinsulatedneutralbusba...

Page 26: ...ls parts components and labor II CHICAGO DIGITAL POWER OF MEXICO SA DE CV will repair the product and if your judgment is not beyond repair to change the team and the defective parts and components thereof without charge to the owner during the warranty period and the cost reasonably incurred transportation of the product resulting from compliance III The repair time will not exceed thirty days fr...

Reviews: