background image

365

UPO33

31<<

>>32

MANUAL 

LOAD 

SHUTDOWN

!

the ups has  entered  the operating  mode 
"manual off total".

!

8#!

+,-31LG)/01,-!
",.*!!

configuration  mode enabled. in  this  mode 
you can modify any parameter of operation of 
the ups. 

 only 

qualified 

personal should access 

the configuration 

mode.

!

8#!

*-.!+,-31LG)/01,-!!

out of configuration mode

!

8#!

0G)-! ,-! "/-G/M!
Ij4/22!!

if you  have a  problem  with  any of  the 
phases, due  to  a problem  in  the inner 
workings  of  the ups, this  alarm is  activated, 
recommending the 

user 

to operate 

the manual bypass.

!

activate 

the manual bypass and 

call service 

center to 

solve the 

problem at ups.

!

BYPASS 

SCR 

FAILURE

!

one of the bypass scrs failed

!

support call

!

Ij4(!),0/01,-!*)),)!!!

the  phase  sequence  of  the  bypass is 
reversed.

!

check  on the terminal  block  of 
the bypass, the 

phases 

are 

connected correctly.

!

BYP. ROTATION OK

!

the  sequence  phases    of  the   bypass,  is 
correct.

!

8#!

UTILITY ABNORMAL

!

this alarm is activated when the voltage at the 
input of the bypass is not adequate to supply 
the  load: the  voltage  is too  high  or 
too low, the frequency is not adequate.

!

check the 

wiring that 

feeds 

the ups. if  the  facility  is good,  wait 
until the entry conditions are normal.

!

BYPASS AVAILABLE

!

the input 

voltage conditions on 

the bypass are 

suitable for 

switching 

to bypass.

!

8#

!

+)101+/M!,c*)M,/.!!

it is activated when you have had an overload 
that has 

lasted longer 

than the ups can 

support, leading tobypass.

!

 

 check  for shorts  to the  output 

•  verify  that

 the  load  does 

not consume  more power  than 
it is capable 

of 

delivering 

the ups

!

INVERTER 

SHUTDOWN A

!

it  is  activated when  the  inverter is  turned 
off because 

it suffers 

an 

internal 

failure of control.

!

support call

!

INVERTER 

SHUTDOWN B

!

it  is  activated when  the  inverter is  turned 
off, because 

it suffers 

an 

internal 

failure of control.

!

support call

!

BATTERY 

the ups batteries are 

depleted. one 

possible cause  is  that  the ups has  operated 

wait  for  the ups input is  normal, 
and start  charging the  batteries. if 

BATTERY 

EXHAUSTED

!

the ups batteries are 

depleted. one 

possible cause  is  that  the ups has  operated 
in battery mode for long.

!

wait  for  the ups input is  normal, 
and start  charging the  batteries. if 
after the  input  is normal, the battery 
will not charge call service.

!

DC FUSE BLOWN

!

the dc fuse is  open. this  happens when  you 
turn the battery breaker before  you turn  on 
the charger when you are starting the ups

!

support call

!

5  V  PWR  SUPPLY 

FAIL

!

the 5v 

supply that 

feeds electronic control failed.

!

support call

!

5  V  PWR  SUPPLY 

OK

!

the 

source 

of 5 

volts that 

powers 

the electronic control works correctly

!

8#!

'H!c!4f)!2G44Mj!3/1M!!

the 13.5v 

supply that 

feeds electronic control failed.

!

support call

!

'H!c!4f)!2G44Mj!,k!!

the  source  of 13.3  volts that  powers 
the electronic control works correctly

!(!

8#!

INVERTER 

OVERFLOW

!

when reading  in  the inverter  output voltage is 
not  reliable because  the  voltage is read 
range the 

electronic 

control. this 

event will bypass the 

ups. this 

condition 

can occur when there are transients.

!

if 

the problem 

persists, 

contact technical support.

!

OVERLOAD 200%

!

there  is an  overload to  the  output more  than 
twice the rating of the ups.

!

 

 check  for shorts  to the  output 

 check  that  the  load does  not 

consume more 

power which 

supplies the ups.

!

0l1!3/1MG)*!!

failure  to transfer  to  the investor. there  is 
an internal 

problem 

that can´t activate 

the inverter.

!

support call

!

INVERTER  COMP. 

FAIL

!

the output voltage of the ups is different from 
the inverter output voltage

!

support call

!

71L7!

L),G-.!

c,M0/L*!

the  voltage between  ground and  neutral is 
too 

high (10 

volts rms). this 

can 

occur because  there  is  no  connection  to 
ground   at  the  facility where ups  or because 
there 

is 

no solid 

connection between 

neutral and ground. another cause may be an 
overload on 

the 

network 

that feeds 

the ups especially if the load is unbalanced.

!

 

 make  sure  the installation 

that is  connected  to ups has 
a grounding. 

 check 

the 

connection 

between ground 

and 

neutral at 

the 

facility 

where the ups. 

•  review  the

 balance of  the 

load.

!

CLR  HIGH  GND 

VOLT

!

activated 

when the 

voltage is 

normalized between  neutral  and  ground, 
after an alarm occurred "neutral-earth high"

!

8#!

Summary of Contents for UPO33

Page 1: ...ual Three PhaseUPS WithIntegratedMonitoringSystem CHICAGO DIGITAL POWER Chicago Digital Power Incorporated 1193 W Higgins Elle Groove Village Il 60007 Tel 847 718 9545 Fax 847 718 9546 www cdpups com 365 UPO33 ...

Page 2: ...r to implementation 6 OPERATING PROCEDURES 6 1 Comissioning 6 2 Total Shutdown 6 3 Normal to electronic bypass transference 6 4 Manual Bypass 6 5 Alarm Reset 7 OPERATION 7 1 Control Panel 7 2 Front cover lights 7 3 LCD operation 7 4 UPSmenudescription 27 7 5 Emergency shutdown 8 ALARMS 8 1 Active alarms 8 2 Alarm reset and UPS normalization 9 COMMUNICATIONS 9 1 RS 232 port 9 2 Net adapter Optional...

Page 3: ... upright Upon receipt of the check the packaging machine which must be in perfect condition no hits no breaks free from excessive moisture otherwise immediately notify the carrier and our company During storage of ups it must be placed in a suitable place where not exposed to direct sunlight or near heat sources such as boilers stoves etc As one should not store near water pipes or in wet envi ron...

Page 4: ... the fit of connectors Here are some safety recommendations during installation operation and maintenance of the UPS All work must be intervention at UPS Realize by qualified personnel Prior to installation of the equipment must verify that all breakers are in the OFF position mainly batteries and must be handled only when the UPS is completely interconnected to rush for strict compliance to the p...

Page 5: ...ver Lights Communication ports RS232 and RJ 45 optional Cooling slots Frontal Panel Lock Front cover lights Communications ports RS232 and RJ 45 optional Cooling Slots Transient supressor Dual Input bypass breaker Optional Input breaker Output breaker Manual bypass breaker Battery breaker Transient supressor Dual input bypass breaker Optional Input breaker Output breaker Manual bypass breaker Batt...

Page 6: ...KJ B 9 EB88JE J9 B KJ C 8 K BD K 8 J JE B8 E U EK V J9 B8 2 d 0KJ K BAJ B8 CB9J UKJ8 KJ J U BCJ B BF BTJ B 9 KJ BD AD KJ J U J J 89 VBTJ KJ 8BC 8 T DJ BF BAJ B8 B KJ V J VJ8EK BB CDEK 9 EK J9 1IFD 8 C 8D V A CB9J UKJ8 KJ B 9 EB88JE J9 9 JE B KJ C 8 K BD K V A E ED K J KJ G42 J F JC 8 D8J8J XJ9 0K CB9J BU KJ D J B BAJ B B E BD E J B GJ 1IFD 18 K BAJ B8 CB9J KJ B 9 EB88JE J9 B KJ C 8 K BD K 8 J JE B...

Page 7: ... inside the UPS is above the nominal value of operation or when the battery pack is deeply discharged In this state the load is powered from the network through the bypass breaker When the UPS is in manual bypass the load is supplied directly from the network through the bypass breaker while the UPS remains de energized This allows maintenance on the UPS without interrupting power to the load In f...

Page 8: ... the input of the UPS before the bat estuaries discharge 5 Press the OFF for five seconds 6 Press the ON for more than six seconds 7 See procedure in Section 6 4 8 See procedure in Section 6 4 9 See procedure in Section 6 2 10 See procedure in Section 6 1 11 Turn off the bypass breaker 12 Switch the bypass breaker 13 When it returns to the input energy and the batteries are discharged 14 See proce...

Page 9: ... 208 VAC There must be a unique breaker to the UPS distribution panel Each line entry and exit should have adequate thickness to withstand the current passing through it The current driving the UPS and hence the sizes of the wires at the entrance and exit agreements changes do to their ability as shown in the following tables FIGURE 4 1 UPS PACKAGING FIGURE 4 2 UPS ANCHORED TO THE PALLET 1 A79 ABC...

Page 10: ...itches are turned off Check that all loads are off Check the polarity of the battery bank h We recommend using a three phase industrial breaker GHEEBGFDHE FBA2DEIJ9 To access the terminals in the ups of 20 kva to 30 kva remove the back cover the terminals are at the bottom in the ups of 40 kva to 80 kva the terminals are located on the front face to access them you must first open the front cover ...

Page 11: ...ILURE and you will hear a beep If this is the case check that batteries are properly connected and the battery breaker is on If when installing the UPS was an error in the phases connection turning on the UPS on the screen appears an alarm FAILURE SEQUENCE BYPASS In this case the UPS will not operate in bypass mode but it will operate in normal mode of operation To solve the problem correctly conn...

Page 12: ...have the correct polarity Turn the output breaker At this point will begin to supply the load through the bypass Turn the manual bypass breaker For the UPS is operating in normal mode press the ON for more than a second It is recommended that the bypass breaker manipulation is done by quali fied personnel 6 5 Alarm Reset See section 8 2 The UPS UPO33 includes a control panel that displays the stat...

Page 13: ...he lights are reds means that the load is being fed to the energy stored in batteries if the lights are flashing red and blue is because the charger is not working properly the cause may be who missed one or two phases to the entrance when the charger starts and if there is no problem the lights are flashing blue and violet if you used the emergency shutdown of the ups the light has a violet color...

Page 14: ... batteries IF the lights are flashing red and blue is because the charger is not working properly The cause may be that missed one or two steps at the entrance When the charger starts and there is no problem if the lights are flashing blue and violet If you use the emergency shutdown of the UPS the light has a violet color 7 3 LCD operation In Figure 7 2 illustrates the operation of the LCD and in...

Page 15: ... all three phases and frequency Table 5 2 Description of the UPS menus 0 4 E H C 8 CJ8D This is the main menu display this screen shows the ups operating status in this case is in normal operation it also displays the web address of manufacturer date and time in this menu you can also update the date and time to make it do the following press three times the enter esc button and the last two digit...

Page 16: ...and the batteries are discharged the causes may be dc fuse open loss of any of the input phases input voltage phase neutral outside the operating range 80 to 150 volts rms check the input voltages call for service RECTIFIER TURN ON is on the battery charger 8 INVERTER TURN ON The invertir is turned on 8 MANUAL INV SHUTDOWN inverter has been turned off manually 8 EMERGENCY PWR OFF emergency shutdow...

Page 17: ...D the ups batteries are depleted one possible cause is that the ups has operated in battery mode for long wait for the ups input is normal and start charging the batteries if after the input is normal the battery will not charge call service DC FUSE BLOWN the dc fuse is open this happens when you turn the battery breaker before you turn on the charger when you are starting the ups support call 5 V...

Page 18: ...battery warning 8 CHECK FANS the blowholes are more than 5 years of use it is advisable to change the FANS to perform the operation contact technical support SELFDIAGNOSTIC alarm information indicates that event counters ups have flooded the memory limit note this does not imply a malfunction of the machine diagnostic is recommended by software call support PWR SUPPLY WARNING it is activated when ...

Page 19: ...ppears when you turn on the ups 8 TEMPERATURE ALERT this alarm occurs when there is a high temperature in the computer but not high enough to go to bypass check the temperature of where the ups is located check the air conditioning system because it may be a fault AMBIENT TEMP OK it is activated when the temperature is at an optimum level after having been high 8 START BATTERY TEST has been initia...

Page 20: ...inverter overflow of the investor check for shorts to the output verify that the load does not consume more power than it is capable of supplying the ups check the temperature of where the ups is located avoid charges that generate large surges in short time if the problem persists call service Ij4 3 Q G0 3 L the frequency of the input bypass is not adequate to power the loads wait until the frequ...

Page 21: ...nd using a USB to serial converter TRENDnet TU S9 Monitoring can be done from a PC using HyperTerminal which is included in Windows versions less than or equal to Windows XP For more recent versions can be down loaded from the Internet Give the connection a name and select an icon and click OK Then in the next window in the Connect using select the port where the UPS is connec ted and click OK see...

Page 22: ...1 4 Click on the button off and then Properties Then see the window shown in Figure 9 1 5 Select the Settings tab and click on the ASCII Setup see Figure 9 1 6 In the next window select the Add linefeed at the end of each line received and click OK to see the window in Figure 9 1 4 and click on the button call ...

Page 23: ...s Additionally provide the UPS MIB to adapt to an environment with a professional monitoring NMS program such as OpenView If allowed the UPS is able to send E MAIL s warning to 8 different email addresses in case of abnormal operating conditions including cell phone numbers The cellular modem allows a GSM network to monitor the UPS status This system allows real time knowledge of the behavior of e...

Page 24: ... normally closed switch thus complementary signals For example when the UPS inverter is operating normally the normally open switch is open and normally closed switch is closed If the inverter fails the normally open switch closes and the normally closed switch will open With the ability to customize the UPS is easy to adapt the UPS to the particular characteristics of virtually any power plant Th...

Page 25: ...oundingsystemgenerally verifyingthattheneutralofthetransformersecondaryoverallsystempowerisreferenced tothispoint Theinputandoutputconductorsmustberoutedtogethertoavoidfeedback andachieveelectromagneticcompatibility Itmustestablishthattheminimumdistancesofventilation maintenanceandoperationof theUPStothewallsorbarriersaround mustbeatleast500mm 50cm Theboardshouldhavearegulatedinsulatedneutralbusba...

Page 26: ...ls parts components and labor II CHICAGO DIGITAL POWER OF MEXICO SA DE CV will repair the product and if your judgment is not beyond repair to change the team and the defective parts and components thereof without charge to the owner during the warranty period and the cost reasonably incurred transportation of the product resulting from compliance III The repair time will not exceed thirty days fr...

Reviews: