INVERTER 

SCR 

FAIL 

!

there  is  an internal  short in  the scr at the 
inverter output.

!

support call

!

UPS  IN  BYPASS 

MODE

!

the ups  is  in operation mode "  electronic  
bypass  "

!

!

8#

!

HIGH 

BYP 

FREQUENCY 

!

the frequency of bypass input is too high.

!

wait 

until the 

frequency 

is normal. if ups is 

fueling a power 

plant, check  it. one  reason may  be 
that the plant fuel is running low.

!

Ij4!3)*QG*-+j!,k!

the frequency of bypass input is normal.

!

8#!

UPS  IN  INVERTER 

MODE

!

the load is being fed through the inverter.

!

8#!

M,f!Ij4!3)*QG*-+j!!!

the frequency of bypass input is too low

!

wait 

until 

the frequency is 

normal. if ups is 

fueling a power 

plant, check  it. one  reason may  be 
that the plant fuelis running low.

!

BYPASS  OUT  OF 

RANGE

!

the bypass voltage is 

beyond 

the recommended 

voltage to 

supply 

equipment in 

accordance 

with ul standards.the charger and inverter are 
still active. this alarm is only informative.

!

to 

increase the 

tolerance 

of 

this alarm, please  contact technical 
support.

!

BYPASS  VOLTAGE 

OK

!

the bypass voltage is 

within 

the recommended 

voltage to 

supply 

equipment in accordance with ul standards.

!

8#!

CLR OVERLOAD

!

it is activated 

when the 

output 

current standard ups, 

having been 

overcharged.

!

8#!

UNBALANCE 

WARNING

!

there  is  a considerable imbalance in  the 
load of 

the 

ups. the 

difference 

in current between  phases  is greater  than 
50% of the rated current.

!

check the balance of the load.

!

+M)!G-I/M/-+*!!

charging  the ups  returns to  rock, after 
submission of an unbalance alarm.

!

8#!

CHECK BATTERIES

!

the  batteries  have more  than  5 years  of 
operation

!

due  to  the operating  history of  the 
batteries is 

recommended 

to 

verify performance and age of these.

!

LOW 

BATTERY 

WARNING

!

the battery is running low

!

turn 

off computers 

that 

are connected  to  the ups as  it  does 
not take much time off.

!

CLR LOW BATTERY

!

the battery has enough charge after the filing 
of a low battery warning.

!

8#!

CHECK FANS

!

the blowholes are more than 5 years of use

!

!

it 

is advisable 

to 

change the 

 

FANS. to 

perform 

the 

operation contact technical support.

!

SELFDIAGNOSTIC

!

alarm information indicates 

that event 

counters ups have  flooded  the memory  limit. 
note: this does not imply a malfunction of the 
machine

!

diagnostic is 

recommended by 

"software", call support

!

PWR 

SUPPLY 

WARNING

!

it  is  activated  when the  control  board has  no 
power.

!

support call

!

CLR  PWR  SUPPLY 

FAIL

!

this 

alarm appears 

when the 

power returned to the  control  board after 
a power alert.

!

8#!

DC OVERVOLTAGE

!!

it  is  activated  when there  has  been 
an excessively  high voltage to  the inverter 
input. this 

alarm may 

be 

generated 

when there  is  a sudden  change of  current  to 
the exit.

!

try 

to 

avoid charges that 

generate large current peaks shortly.

!

.+!,c*)3M,f!!

when the 

reading 

on 

the charger 

output voltage is  not  reliable, because  the 
voltage is  not  in the  read  range ofelectronic 
control. this 

event will 

take 

the ups to 

bypass. this  condition  can occur  when there 
are transients.

!

if  the  problem persists,  call for 
service.

!

CLR DC OVERFLOW

!

when  the  voltage  on the  charger  output is 
back  in the  read  range  of electronic 
control after an alarm"overflow dc".

!

8#!

FLASH MISMATCH

!

it  occurs when  changing  a parameter  that 
can affect the normal operation of the ups.

!

not  manipulate the  settings  menu, 
it should be handled only by qualified 
personnel.

!

FLASH UPDATED

!

occurs  when any  parameter  of operation 
of the ups is modified.

!

8#!

TRANSFM 

TEMPERATURE

!

the transformer 

temperature is 

above 

the recommended  limit  for the  proper 
functioning of 

the ups and 

can 

affect battery life.

!

check 

the 

temperature of 

where the ups is 

located. 

check the air conditioning system, as 
it may be a fault

!

1LI0!0*"4*)/0G)*!

igbt temperature is  above  the recommended 

limit for the proper functioning of the ups and 

can 

affect batterylife. 

this  may  cause a  malfunction in  the 

inverter and reduce the efficiency of the ups.

 

check 

the 

temperature of 

where the ups is 

located. 

check the air conditioning system, as 

Summary of Contents for UPO33

Page 1: ...ual Three PhaseUPS WithIntegratedMonitoringSystem CHICAGO DIGITAL POWER Chicago Digital Power Incorporated 1193 W Higgins Elle Groove Village Il 60007 Tel 847 718 9545 Fax 847 718 9546 www cdpups com 365 UPO33 ...

Page 2: ...r to implementation 6 OPERATING PROCEDURES 6 1 Comissioning 6 2 Total Shutdown 6 3 Normal to electronic bypass transference 6 4 Manual Bypass 6 5 Alarm Reset 7 OPERATION 7 1 Control Panel 7 2 Front cover lights 7 3 LCD operation 7 4 UPSmenudescription 27 7 5 Emergency shutdown 8 ALARMS 8 1 Active alarms 8 2 Alarm reset and UPS normalization 9 COMMUNICATIONS 9 1 RS 232 port 9 2 Net adapter Optional...

Page 3: ... upright Upon receipt of the check the packaging machine which must be in perfect condition no hits no breaks free from excessive moisture otherwise immediately notify the carrier and our company During storage of ups it must be placed in a suitable place where not exposed to direct sunlight or near heat sources such as boilers stoves etc As one should not store near water pipes or in wet envi ron...

Page 4: ... the fit of connectors Here are some safety recommendations during installation operation and maintenance of the UPS All work must be intervention at UPS Realize by qualified personnel Prior to installation of the equipment must verify that all breakers are in the OFF position mainly batteries and must be handled only when the UPS is completely interconnected to rush for strict compliance to the p...

Page 5: ...ver Lights Communication ports RS232 and RJ 45 optional Cooling slots Frontal Panel Lock Front cover lights Communications ports RS232 and RJ 45 optional Cooling Slots Transient supressor Dual Input bypass breaker Optional Input breaker Output breaker Manual bypass breaker Battery breaker Transient supressor Dual input bypass breaker Optional Input breaker Output breaker Manual bypass breaker Batt...

Page 6: ...KJ B 9 EB88JE J9 B KJ C 8 K BD K 8 J JE B8 E U EK V J9 B8 2 d 0KJ K BAJ B8 CB9J UKJ8 KJ J U BCJ B BF BTJ B 9 KJ BD AD KJ J U J J 89 VBTJ KJ 8BC 8 T DJ BF BAJ B8 B KJ V J VJ8EK BB CDEK 9 EK J9 1IFD 8 C 8D V A CB9J UKJ8 KJ B 9 EB88JE J9 9 JE B KJ C 8 K BD K V A E ED K J KJ G42 J F JC 8 D8J8J XJ9 0K CB9J BU KJ D J B BAJ B B E BD E J B GJ 1IFD 18 K BAJ B8 CB9J KJ B 9 EB88JE J9 B KJ C 8 K BD K 8 J JE B...

Page 7: ... inside the UPS is above the nominal value of operation or when the battery pack is deeply discharged In this state the load is powered from the network through the bypass breaker When the UPS is in manual bypass the load is supplied directly from the network through the bypass breaker while the UPS remains de energized This allows maintenance on the UPS without interrupting power to the load In f...

Page 8: ... the input of the UPS before the bat estuaries discharge 5 Press the OFF for five seconds 6 Press the ON for more than six seconds 7 See procedure in Section 6 4 8 See procedure in Section 6 4 9 See procedure in Section 6 2 10 See procedure in Section 6 1 11 Turn off the bypass breaker 12 Switch the bypass breaker 13 When it returns to the input energy and the batteries are discharged 14 See proce...

Page 9: ... 208 VAC There must be a unique breaker to the UPS distribution panel Each line entry and exit should have adequate thickness to withstand the current passing through it The current driving the UPS and hence the sizes of the wires at the entrance and exit agreements changes do to their ability as shown in the following tables FIGURE 4 1 UPS PACKAGING FIGURE 4 2 UPS ANCHORED TO THE PALLET 1 A79 ABC...

Page 10: ...itches are turned off Check that all loads are off Check the polarity of the battery bank h We recommend using a three phase industrial breaker GHEEBGFDHE FBA2DEIJ9 To access the terminals in the ups of 20 kva to 30 kva remove the back cover the terminals are at the bottom in the ups of 40 kva to 80 kva the terminals are located on the front face to access them you must first open the front cover ...

Page 11: ...ILURE and you will hear a beep If this is the case check that batteries are properly connected and the battery breaker is on If when installing the UPS was an error in the phases connection turning on the UPS on the screen appears an alarm FAILURE SEQUENCE BYPASS In this case the UPS will not operate in bypass mode but it will operate in normal mode of operation To solve the problem correctly conn...

Page 12: ...have the correct polarity Turn the output breaker At this point will begin to supply the load through the bypass Turn the manual bypass breaker For the UPS is operating in normal mode press the ON for more than a second It is recommended that the bypass breaker manipulation is done by quali fied personnel 6 5 Alarm Reset See section 8 2 The UPS UPO33 includes a control panel that displays the stat...

Page 13: ...he lights are reds means that the load is being fed to the energy stored in batteries if the lights are flashing red and blue is because the charger is not working properly the cause may be who missed one or two phases to the entrance when the charger starts and if there is no problem the lights are flashing blue and violet if you used the emergency shutdown of the ups the light has a violet color...

Page 14: ... batteries IF the lights are flashing red and blue is because the charger is not working properly The cause may be that missed one or two steps at the entrance When the charger starts and there is no problem if the lights are flashing blue and violet If you use the emergency shutdown of the UPS the light has a violet color 7 3 LCD operation In Figure 7 2 illustrates the operation of the LCD and in...

Page 15: ... all three phases and frequency Table 5 2 Description of the UPS menus 0 4 E H C 8 CJ8D This is the main menu display this screen shows the ups operating status in this case is in normal operation it also displays the web address of manufacturer date and time in this menu you can also update the date and time to make it do the following press three times the enter esc button and the last two digit...

Page 16: ...and the batteries are discharged the causes may be dc fuse open loss of any of the input phases input voltage phase neutral outside the operating range 80 to 150 volts rms check the input voltages call for service RECTIFIER TURN ON is on the battery charger 8 INVERTER TURN ON The invertir is turned on 8 MANUAL INV SHUTDOWN inverter has been turned off manually 8 EMERGENCY PWR OFF emergency shutdow...

Page 17: ...D the ups batteries are depleted one possible cause is that the ups has operated in battery mode for long wait for the ups input is normal and start charging the batteries if after the input is normal the battery will not charge call service DC FUSE BLOWN the dc fuse is open this happens when you turn the battery breaker before you turn on the charger when you are starting the ups support call 5 V...

Page 18: ...battery warning 8 CHECK FANS the blowholes are more than 5 years of use it is advisable to change the FANS to perform the operation contact technical support SELFDIAGNOSTIC alarm information indicates that event counters ups have flooded the memory limit note this does not imply a malfunction of the machine diagnostic is recommended by software call support PWR SUPPLY WARNING it is activated when ...

Page 19: ...ppears when you turn on the ups 8 TEMPERATURE ALERT this alarm occurs when there is a high temperature in the computer but not high enough to go to bypass check the temperature of where the ups is located check the air conditioning system because it may be a fault AMBIENT TEMP OK it is activated when the temperature is at an optimum level after having been high 8 START BATTERY TEST has been initia...

Page 20: ...inverter overflow of the investor check for shorts to the output verify that the load does not consume more power than it is capable of supplying the ups check the temperature of where the ups is located avoid charges that generate large surges in short time if the problem persists call service Ij4 3 Q G0 3 L the frequency of the input bypass is not adequate to power the loads wait until the frequ...

Page 21: ...nd using a USB to serial converter TRENDnet TU S9 Monitoring can be done from a PC using HyperTerminal which is included in Windows versions less than or equal to Windows XP For more recent versions can be down loaded from the Internet Give the connection a name and select an icon and click OK Then in the next window in the Connect using select the port where the UPS is connec ted and click OK see...

Page 22: ...1 4 Click on the button off and then Properties Then see the window shown in Figure 9 1 5 Select the Settings tab and click on the ASCII Setup see Figure 9 1 6 In the next window select the Add linefeed at the end of each line received and click OK to see the window in Figure 9 1 4 and click on the button call ...

Page 23: ...s Additionally provide the UPS MIB to adapt to an environment with a professional monitoring NMS program such as OpenView If allowed the UPS is able to send E MAIL s warning to 8 different email addresses in case of abnormal operating conditions including cell phone numbers The cellular modem allows a GSM network to monitor the UPS status This system allows real time knowledge of the behavior of e...

Page 24: ... normally closed switch thus complementary signals For example when the UPS inverter is operating normally the normally open switch is open and normally closed switch is closed If the inverter fails the normally open switch closes and the normally closed switch will open With the ability to customize the UPS is easy to adapt the UPS to the particular characteristics of virtually any power plant Th...

Page 25: ...oundingsystemgenerally verifyingthattheneutralofthetransformersecondaryoverallsystempowerisreferenced tothispoint Theinputandoutputconductorsmustberoutedtogethertoavoidfeedback andachieveelectromagneticcompatibility Itmustestablishthattheminimumdistancesofventilation maintenanceandoperationof theUPStothewallsorbarriersaround mustbeatleast500mm 50cm Theboardshouldhavearegulatedinsulatedneutralbusba...

Page 26: ...ls parts components and labor II CHICAGO DIGITAL POWER OF MEXICO SA DE CV will repair the product and if your judgment is not beyond repair to change the team and the defective parts and components thereof without charge to the owner during the warranty period and the cost reasonably incurred transportation of the product resulting from compliance III The repair time will not exceed thirty days fr...

Reviews: