13
cdvigroup.com
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
EN
AIOM
10-Input/10-Output Module
INSTALLATION MANUAL
5] WIRING DIAGRAM
Connecting the Box Tamper Switches
Connecting the tamper switches allows the AIOM Module to detect when the cabinet door is opened and/or
when the cabinet is removed from the wall. To install the tamper switches, see “Installing the Tamper Switches”.
To use both switches:
1. Connect one end of the supplied wire, the one with a log at each end, to the door tamper switch
terminal and the other end to the wall tamper switch terminal.
2. Connect the other terminal of the door tamper switch to the “TMP” terminals using the supplied wire.
3. Connect the other terminal of the wall tamper switch to the “GND” terminals using the supplied wire.
To use only one switch:
1. Connect one terminal of the tamper switch to the “TMP” terminals using the supplied wire.
2. Connect the other terminal of the same tamper switch to the “GND” terminals using the supplied wire.
If you do not use the tamper switch, connect a wire between the “TMP” and “GND” terminals.
INPUTS
INPUTS
OUTPUTS
OUTPUTS
TMP/SMOKE
LOCAL BUS
Metal Box
Door Tamper Switch
(N.C.)
Metal Box
Wall Tamper Switch
(N.C.)
AIOM
Input / Output Module
Summary of Contents for AIOM
Page 1: ...AIOM The installer s choice cdvigroup com ENGLISH EN 10 Input 10 Output Module ...
Page 21: ...21 cdvigroup com EN AIOM 10 Input 10 Output Module INSTALLATION MANUAL NOTES ...
Page 22: ...22 cdvigroup com EN AIOM 10 Input 10 Output Module INSTALLATION MANUAL NOTES ...
Page 23: ...23 cdvigroup com EN AIOM 10 Input 10 Output Module INSTALLATION MANUAL NOTES ...