14. Maintenance
Maintenance shall only be performed by properly trained people.
14.1 Access Inview with Laptop
•
Download system LOG FILE and save.
- Analyze log file and correct errors.
•
Download system CONFIGURATION FILE and save.
- Check/correct configuration file according to operation conditions.
- Check/correct alarm configuration.
•
Check module internal temperature for deviation between modules.
- Temperature deviation may indicate build up of dust. Clean the module by air suction blower or vacuum
cleaner.
•
Check module/system load.
•
Check/Correct inverter mapping (DC group/AC group/ Address).
•
Change configuration file to validate that system operates on both supply sources.
•
Check outgoing alarm, consult configuration file what actions will generate alarm.
14.2 Manual check
•
Validate input voltage (AC input, DC input, AC output) with multi-meter.
•
Replace dust filter.
14.3 Optional
•
With an infrared camera check termination hot spots.
- Tighten terminations.
14.4 Manual By-Pass
•
Make sure AC input source is available during MBP operation. Otherwise the LOAD will be affected.
Maintenance
41
- Bravo 10 - 48/230 - User manual - v1.2
Summary of Contents for Bravo 10 - 48/230
Page 43: ......