background image

7. SPECIFICATION

TECHNICAL DATA

Transmission Parameters

Interface

RS-232

Current Loop

Connector

 DSUB-9 female

Screw terminal, wire max. Ø 2,5mm

2

.

Line length

15m

Depend on baud rate eg. For bus made 

by UTP cable Cat.5E 4x2x05 (24 AWG) 

and baud rate 19200 bit/s the line length 

up to 1000m. 

Maximum number of connected device

1

1

Transmission line

DB9F/DB9M multicore cable  9x0,34 

shielded (up to 15m) or 9-pair twisted 

cable, UTP 9x2x0,5 (24AWG) shield inside

large interferences STP 9x2x0,5 (24AWG).

2-pair twisted cable eg UTP Nx2x0,5 

(24AWG), shield inside large 

interferences eg STP Nx2x0,5 (24AWG).

Standards

RS-232C /CCITTV.24

current signal, 0-20mA 

Maximum baud rate

38,4 kbps (depend on length of Current Loop line)

Transmission type 

Current Loop asynchronous half duplex or full duplex

Optical signalization

PWR – green LED power supply,

RX - red LED data receiving from Current Loop side,

TX - yellow LED data transmission through Current Loop interface.

Electrical Parameters

Power requirements

10 - 24 – 30 V DC

Power cable

Recommended length of power cable < 3m

Power

<3W

Protection from reverse power polarization

YES

Galvanic isolation

1kV= or 3kV= ( between power circuit and  RS-232 signal line)

1kV= or 3kV= (between power circuit and Current Loop signal line)

Optoisolation

~3kV= (between signal lines Current Loop and RS-232)

Electromagnetic compatibility

Resistance to disruptions according to the standard PN-EN 55024.

Emission of disruptions according to the standard PN-EN 55022.

Safety requiring

According to the PN-EN60950 norm.

Environment

Commercial and light industrial.

Environmental Parameters

Operating temperature

-30 ÷ 60°C

Humidity

5 ÷ 95% - non-condensing

Storage temperature

-40 ÷ 70°C

Casing

Dimensions

53mm x 90mm x 62 mm,

Material

Noryl UL. 94 V-O

Degree of casing protection

IP40

Degree of terminal protection

IP20

Weight

0,10 kg

According to standards

DIN EN50022, DIN EN43880

Location during work

Free

Mounting method

On the rail compliant with DIN35 / TS35 standard.

11

ADA-1021

Summary of Contents for ADA-1021

Page 1: ...User manual ADA 1021 RS 232 to Current Loop Converter 1 io_ada 1021_v1 02_en Copyright 2001 2017 CEL MAR sp j ADA 1021...

Page 2: ...ECTION OF DEVICES WITH RS232 PORT DCE TYPE MODEM 6 3 3 CONNECTION OF CURRENT LOOP DEVICES 7 3 3 1 CONNECTION TO DEVICE WITH PASSIVE TRANSMITTER PASSIVE RECEIVER 7 3 3 2 CONNECTION TO DEVICE WITH ACTIV...

Page 3: ...ps and the like Complete disable from the supply network is only after disconnecting the power supply circuit voltage Do not carry out the assembly or dis assembly of the device if it is enabled This...

Page 4: ...converter RTS signal is looped with CTS inside the converter and DTR with DSR and DCD Others signals are not connected If it is not needed looping the above signals can be unsolder the RTS or DTR in t...

Page 5: ...cables in the distance not shorter than 25 cm from powering cables apply cable of adequate cross section due to voltage drops for converter powering use Interference suppression filters for power supp...

Page 6: ...lable in CEL MAR offer Example connection is shown below Fig 6 Connection to device with RS232 type DCE 6 ADA 1021 RxD 2 TxD 3 DTR 4 DSR 6 RTS 7 CTS 8 PC SG 5 RS232 DTE DB 9M ADA 1021 Current Loop Vss...

Page 7: ...with active transmitter and active receiver to ADA 1021 7 ADA 1021 ADA 1021 V V Power Tx Tx Rx Rx Current Loop Device I1 I1 I2 I2 Rx Current Loop connector Tx Tx Rx V V Active Transmitter Active Recei...

Page 8: ...21 ADA 1021 Active transmitter Power Tx Tx Rx Rx Current Loop Device I1 I1 I2 I2 Rx Passive receiver Tx Tx Rx Current Loop connector Current Loop connector V V V V Passive Receiver Active Transmitter...

Page 9: ...RTS 7 CTS 8 PC SG 5 RS232 DTE DB 9M ADA 1020 Current Loop Vss Vss Power Supply RS232 DCE DB 9F CTS 7 RTS 8 GND 5 V V Tx 2 Rx 3 DSR 4 DTR 6 2 3 4 6 7 8 5 CAB DB 9F DB9M S 1 8m cable Socked DB 9F 2 3 4...

Page 10: ...PWR Signalization of power supply RX Signalization of data receiving by ADA 1021 from Current Loop TX Signalization of data transmission from ADA 1021 converter through Current Loop ATTENTION AT BAUD...

Page 11: ...ow LED data transmission through Current Loop interface Electrical Parameters Power requirements 10 24 30 V DC Power cable Recommended length of power cable 3m Power 3W Protection from reverse power p...

Page 12: ...transmission converters with interface RS232 RS485 RS422 USB Current Loop Fibre Optic Converters and Ethernet or Wi Fi Please contact us to tell how you like our products and how we can satisfy you p...

Reviews: