Dimensions (W x D x H) 53mm x 62mm x 90mm.

2.2. DESCRIPTION

Many devices  such  as  PLCs, transducers,  sensors,  cash  registers  and  electronic  scales  are equipped  with  as standard  RS232

communication port. Standard of RS232 has restrictions on the length of the cable (the distance at which the transmission is working

properly is 15m). The solution to this problem is to use for data transmission Current Loop interface. Current Loop Interface allows to

connect with each other devices at up to several kilometres.

ADA-1021 converter is a device used to convert RS232 to Current Loop standard without interfering with data format. The converter

does not require the power to his operation from the RS232 port, supports asynchronous RS232 data transmission at up to 38.4 kbps

by two pairs of twisted-pair. ADA-1021 is equipped with a female DB-9F connector for RS232 interface connection and screw terminal

blocks for twisted-pair connections of Current Loop and power supply. DB-9 connector is made as DCE which allows to connect the

converter to the PC via the RS232 extension cable (a typical cable modem connection) without crossing Tx with Rx and RTS with

CTS. For its operation uses the signals from the RX, TX and mass SG, entered by DB-9F connector to the converter. RTS signal is

looped with CTS inside the converter and DTR with DSR and DCD. Others signals are not connected. If it is not needed looping the

above signals, can be unsolder the RTS or DTR in the plug DB-9M (pins: RTS-7, DTR-4). To Current Loop line constructed on the

ADA-1021 can be connected two converters operating in full duplex or half duplex point-to-point.

This   converter   has   internal,   low   energy   surge   protection   (600W   overvoltage   diodes)   for   each   Current   Loop   lines   however   it   is

recommended to use the external 

 

 lightning arresters (typical protection of telephone line) for the lightning protection of lines. 

Fig. 1. View

2.3. CURRENT LOOP TRANSMITTER

The Current Loop transmitter in the ADA-1021 was made as a passive 0-20mA, having low energy short circuit protection on TX+ and

TX- lines. By the correct connection of the transmitter with power source I1, Current Loop transmitter 0-20mA can operate as active.

The transmitter diagram is shown on figure below.

2.4. CURRENT LOOP RECEIVER

The ADA-1021 converter has passive RX receiver having  low energy short circuit protection on TX+ and TX- lines.

By the correct connection of the receiver with power source I2, Current Loop receiver 0-20mA can operate as active. 

4

ADA-1021

(RS-232)

I1

 +

T

+

T

-

I1

 -

I2

 +

R

+

R

-

I2

 -

(CURRENT LOOP)

V

 -

V

 +

10 – 30 

VDC

PWR

TX

RX

ADA-1021

RS-232 to CURRENT LOOP

CONVERTER

CL

62mm

 RS-232 interface

DB-9F connector

Power supply

10-24-30 VDC

53mm

1

0

m

m

6

m

m

9

0

m

m

Current Loop Interface

Summary of Contents for ADA-1021

Page 1: ...User manual ADA 1021 RS 232 to Current Loop Converter 1 io_ada 1021_v1 02_en Copyright 2001 2017 CEL MAR sp j ADA 1021...

Page 2: ...ECTION OF DEVICES WITH RS232 PORT DCE TYPE MODEM 6 3 3 CONNECTION OF CURRENT LOOP DEVICES 7 3 3 1 CONNECTION TO DEVICE WITH PASSIVE TRANSMITTER PASSIVE RECEIVER 7 3 3 2 CONNECTION TO DEVICE WITH ACTIV...

Page 3: ...ps and the like Complete disable from the supply network is only after disconnecting the power supply circuit voltage Do not carry out the assembly or dis assembly of the device if it is enabled This...

Page 4: ...converter RTS signal is looped with CTS inside the converter and DTR with DSR and DCD Others signals are not connected If it is not needed looping the above signals can be unsolder the RTS or DTR in t...

Page 5: ...cables in the distance not shorter than 25 cm from powering cables apply cable of adequate cross section due to voltage drops for converter powering use Interference suppression filters for power supp...

Page 6: ...lable in CEL MAR offer Example connection is shown below Fig 6 Connection to device with RS232 type DCE 6 ADA 1021 RxD 2 TxD 3 DTR 4 DSR 6 RTS 7 CTS 8 PC SG 5 RS232 DTE DB 9M ADA 1021 Current Loop Vss...

Page 7: ...with active transmitter and active receiver to ADA 1021 7 ADA 1021 ADA 1021 V V Power Tx Tx Rx Rx Current Loop Device I1 I1 I2 I2 Rx Current Loop connector Tx Tx Rx V V Active Transmitter Active Recei...

Page 8: ...21 ADA 1021 Active transmitter Power Tx Tx Rx Rx Current Loop Device I1 I1 I2 I2 Rx Passive receiver Tx Tx Rx Current Loop connector Current Loop connector V V V V Passive Receiver Active Transmitter...

Page 9: ...RTS 7 CTS 8 PC SG 5 RS232 DTE DB 9M ADA 1020 Current Loop Vss Vss Power Supply RS232 DCE DB 9F CTS 7 RTS 8 GND 5 V V Tx 2 Rx 3 DSR 4 DTR 6 2 3 4 6 7 8 5 CAB DB 9F DB9M S 1 8m cable Socked DB 9F 2 3 4...

Page 10: ...PWR Signalization of power supply RX Signalization of data receiving by ADA 1021 from Current Loop TX Signalization of data transmission from ADA 1021 converter through Current Loop ATTENTION AT BAUD...

Page 11: ...ow LED data transmission through Current Loop interface Electrical Parameters Power requirements 10 24 30 V DC Power cable Recommended length of power cable 3m Power 3W Protection from reverse power p...

Page 12: ...transmission converters with interface RS232 RS485 RS422 USB Current Loop Fibre Optic Converters and Ethernet or Wi Fi Please contact us to tell how you like our products and how we can satisfy you p...

Reviews: