4.5. PROBLEMS
Problem
Solutions
PWR LED is not lights.
Check polarization and parameters of connected power supply.
Rx LED lights continuously
RS485(4W) /RS422 bus. Wrong polarization on Rx+, Rx- terminals. Change polarization.
RS485(2W) bus. Wrong polarization on Tx+/A, Tx-/B terminals. Change polarization.
No transmission,
Tx LED is blinking
RS485(4W) /RS422 bus. Check the correctness of connection to Tx, Rx terminals according
to chapter 3.
RS485(2W) bus. Check the correctness of configuration setting according to chapter 4.
5. RS232 INTERFACE – PIN DESCRIPTION OF DSUB-9F-DCE SOCKET
Pin
Signal
Description
ADA-1040
1 (DCD)
Level of receiver signal
Connected with DSR
2 (TxD)
Data transmission via ADA-1040
Transmitter
3 (RxD)
Data receiving via ADA-1040
Receiver
4 (DSR)
Readiness of receiving via ADA-1040
Receiver (in ADA-1040-x-2-x-x)
Connected with DTR (in ADA-1040-x-1-x-x)
5 (SG)
Signal ground
GND
6 (DTR)
Readiness of data receiving/ transmission from ADAI1040
Receiver (in ADA-1040-x-2-x-x)
Connected with DSR (in ADA-1040-x-1-x-x)
7 (CTS)
Readiness of transmission to ADA-1040
Connected with RTS
8 (RTS)
Demand of transmission from ADA-1040
Connected with CTS
9 (RI)
Call rate
Connected with
+5VDC
of converter's in versions:
ADA-1040-x-19-x-x,
ADA-1040-x-29-x-x.
Not connected in other versions.
6. VERSIONS
ADA-1040 -
-
-
-
Order example:
Product Symbol:
ADA-1040-1-1-23-3
1
– basic version of electronic,
1
– TX, RX signals
23
- galvanic isolation 1kV=, 3-way
3
- cover without inlets, plug-in screw
terminal block,
Electronic versions:
Basic,
1
Special,
2
Signals:
TX, RX
1
TX, RX . +5VDC on 9 pin of RS232 DB-9F connector
19
TX, RX, DTR, DSR – only in version 2-way isolation
2
TX, RX, DTR, DSR +5VDC on 9 pin of RS232 DB-9F connector
– only in version 2-way isolation
29
Galvanic isolation:
1kV= 2-way
2
1kV= 3-way
23
3kV= 2-way
3
3kV= 3-way
33
Terminal & Terminal Cover:
Cover without inlets, screw terminal block
1
Cover with inlets, screw terminal block
2
Cover without inlets, plug-in screw terminal block
3
10
ADA-1040