5.2.  DESCRIPTION OF SIGNALLING LEDS 

LED

Description

PWR

Signalling of Power Supply

RUN mode

RX

Signalling of data receiving through ADA-1040D from RS485 port

TX

Signalling of data transmitting from ADA-1040D through RS485 port

Configuration mode

LINK (by SW1) Blink with frequency 1 Hz - signalling of configuration mode (see micro-switch SW1 setting)

Firmware update mode

LINK (by SW1) Blinking signalling software data flows to converter.

Improper connection of converters, break for RS485 (4W) / 422 bus

LINK (by SW1) Blink with frequency 10Hz - signalling of no communication between the converters on 

RS485(4W)/RS422 bus (break the link, no connection of converters).

ATTENTION!

AT BAUD RATE ABOVE 38.4 KBPS THE LED'S TX, RX WILL LIGHT WEAKLY DURING DATA TRANSMISSION

6. CONFIGURATION

6.1. HARDWARE CONFIGURATION

Hardware configuration of ADA-1040D is done by setting of SW1 micro-switch to suitable operating mode.
The SW1 located by terminal block RS232. To set the switch section, should remove terminal cover marked as SW1 and make the
appropriate settings by the use a small, flat screwdriver. 

6.1.1. OPERATION MODE

 ADA-1040D converter can operates in a few modes:

run,

configuration,

factory default,

emergency firmware update

Those modes can be set by use SW1 located by DB-9F connector, labelled as RS232. To set the switch section, should remove the
cover marked as SW1 and make the appropriate settings by the use a small, flat screwdriver. 
All  available   adjusting   the   SW1  switch   are  shown   in  table   below.  If  there   are  additional   question   please   contact   with  technical
department: +48 41 362-12-46

Converter operation modes

SW1- 1

SW1- 2

Mode

OFF

OFF

Run

ON

OFF

Configuration

OFF

ON

Factory default

Turning OFF and ON the power of the converter, the configuration will be set

to factory default.

ON

ON

Emergency Firmware Update

6.2. CONFIGURATION BY USING ADACONFIG

The configuration of ADA-1040D converter can be made by the use of 

ADAConfig

 Software - selling with converter.

To make the configuration, connect converter to computer and power supply.  If after power, on the front panel is not lit green LED
PWR, check the power connection (polarity). If the PWR LED lights, set the section of SW1 switch to configuration mode as in table
below.

SW1-1

SW1-2

ON

OFF

In the configuration mode the yellow LED located by SW1 micro-switch will blink with frequency 1 Hz. Start the ADAConfig Software
and make the configuration of transmission parameters for  each converter interfaces  RS-232 and RS485.  First, should be set the
number of COM port for communication with the converter, then readout the configuration from ADA-1040D memory using the button

[Read converter configuration]

 and make the proper changes of each interfaces setting. 

6.2.1. CONFIGURATION OF RS232 INTERFACE

After readout the configuration, for RS232 interface can be set parameters:

– baud rate (kbps): 0.3, 0.6, 1.2, 1.8, 2.4, 4.8, 7.2, 9.6, 14.4, 19.2, 28.8, 38.4, 57.6, 76.8, 115.2, 230.4,
– number of data bites: 5, 6, 7, 8,

9

ADA-1040D

Summary of Contents for ADA-1040D

Page 1: ...User manual ADA 1040D RS 232 to RS 485 4W RS 422 digital converter 1 io_ada 1040d_v1 11_en Copyright 2001 2020 CEL MAR sp j ADA 1040D...

Page 2: ...7 4 3 1 GND TERMINAL CONNECTION 7 4 3 2 LINE TERMINATION Rt 7 4 3 3 EXAMPLE CONNECTION OF CONVERTER AS THE EXTENSION PORT RS232 PC 8 4 4 POWER SUPPLY CONNECTION 8 5 ACTIVATION 8 5 1 TROUBLESHOOTING 8...

Page 3: ...assembly or disassembly of the device if it is enabled This may result to short circuit and damage the device The device can not be used for applications that determine human life and health eg Medic...

Page 4: ...bus is made by the use of 2 pairs twisted cable The converter has the connection control for testing the correctness connection of RS485 4W bus with him ADA 1040D is equipped with DSUB 9 female conne...

Page 5: ...s of using the converter as extender of RS232 PC port Fig 3 Operating principle of ADA1040D Fig 4 Example connection of a cash register with RS232 interface to PC 1200 m away 5 ADA 1040D Cash register...

Page 6: ...MBLING ADA 1040D converter case is adapted to assembly on TS 35 DIN35 rail To install converter should mount device on the rail upper part of the case then press bottom part to hearing characteristic...

Page 7: ...tallation signals grounds of other devices 4 3 2 LINE TERMINATION Rt The application of Line Termination terminator Rt 120 W ohms will reduce electrical reflection in data line at high baud rate It is...

Page 8: ...onnection is there no break or short circuit of the bus is there connected the converter on the other side of the bus to power supply 10 30VDC stabilized are there set the same baud rate on RS485 4W R...

Page 9: ...riate settings by the use a small flat screwdriver All available adjusting the SW1 switch are shown in table below If there are additional question please contact with technical department 48 41 362 1...

Page 10: ...smission parameters to the length of RS485 422 bus Available baud rates kbps 0 3 0 6 1 2 1 8 2 4 4 8 7 2 9 6 14 4 19 2 28 8 38 4 57 6 76 8 115 2 230 4 ATTENTION IN BOTH CONVERTERS CREATING CONNECTION...

Page 11: ...onverter ports After finishing the diagnostics the SW1 microswitch should be set to the run mode as shown in the table below SW1 1 SW1 2 OFF OFF The yellow LED located near the SW1 will turn off 6 4 F...

Page 12: ...t the power and after while connect again After that will be loaded the factory default setting Parameters are as follows RS232 RS485 4W 422 Baud rate 9600 bps Baud rate 19200 bps 8 data bits 8 data b...

Page 13: ...EIA 485 CCITT V 11 Max baud rate 230 4 kbps Transmission type Asynchronous full duplex half duplex Optical Signalization PWD green LED power supply RX red LED data receiving on RS485 RS422 TX yellow L...

Page 14: ...According to standards DIN EN50022 DIN EN43880 Location during work Free Mounting Rail mounting according to DIN35 standard TS35 14 ADA 1040D...

Page 15: ...15 ADA 1040D...

Page 16: ...transmission converters with interface RS232 RS485 RS422 USB Current Loop Fibre Optic Converters and Ethernet or Wi Fi Please contact us to tell how you like our products and how we can satisfy you pr...

Reviews: