Return to work in RUN mode is made by using SW1 switch as below.
SW1-1
SW1-2
OFF
OFF
In the RUN mode the yellow LED (located near the SW1), will turn off.
Fig.9. View of ADAConfig software interface
5.3. FACTORY DEFAULT
In case of faulty functioning ADA-1040PC3, can be restored the factory default setting of the converter internal registers.
Set SW1 microswitch mode as in the table below.
SW1-1
SW1-2
OFF
ON
Disconnect
the power and after while
connect
again the power. After that, will be loaded the factory default setting to the converter
internal registers.
After this operation, the converter parameters should be set again for operating in the application.
Set micro switch SW1 to run mode as shown in the table below.
SW1-1
SW1-2
OFF
OFF
In the run mode the yellow LED (located near the SW1), will turn off.
5.4. FIRMWARE UPDATE
Set SW1 micro switch to configuration mode as in table below.
SW1-1
SW1-2
ON
OFF
10
ADA-1040PC3
Summary of Contents for ADA-1040PC3
Page 23: ...23 ADA 1040PC3...