11. SPECIFICATION
TECHNICAL DATA
Transmission Parameters
Interface
RS-232
RS-485/RS-422
Connector
DSUB-9 socket, female
Screw terminal, wire max. Ø 2,5mm
2
Line length
up to 15m
1200m
Interface
1
32
Transmission line
DB9F/DB9M cable, multicore 9x0,34
shielded (up to 15m)
Twisted cable 1-pair or 2-pair , UTP Nx2x0,5
(24AWG), shield inside large interferences
STP Nx2x0,5(24AWG)
Standards
EIA-232, CCITT V.24,
EIA-485, CCITT V.11
Protocol
SunMaster
Modbus-RTU
Baud rate
9600bps 8/N/1
Do 230,4 kbps
Transmission type
Asynchronism full duplex, half duplex.
Optical signalisation
•
PWR – green LED power supply,
•
RX - red LED data receiving from RS485/RS422 interface,
•
TX - yellow LED data transmission through RS485/RS422 interface.
Electrical Parameters
Power requirements
10 - 24 – 30 V DC
Power Cable
Recommended length of power cable – up to 3m.
Power
< 2W
Protection from reverse power polarization
Yes
Galvanic Isolation
1kVDC or 3kVDC, between power circuit and RS232 and RS485/422 signal line,
Optoisolation
~3kV - between signal line RS-232 and RS485/422.
Electromagnetic compatibility
Resistance to disruptions according to the standard PN-EN 55024.
Emission of disruptions according to the standard PN-EN 55022.
Safety requiring
According to the PN-EN60950 norm.
Environment
Commercial and light industrial.
Environmental Parameters
Operating temperature
-30 ÷ 60°C
Humidity
5 ÷ 95% - non-condensing
Storage temperature
-40 ÷ 70°C
Casing
Dimensions
53 x 90 x 62 mm
Material
Noryl UL. 94 V-O
Degree of casing protection
IP40
Degree of terminal protection
IP20
Weight
0,10 kg
According to standard
DIN EN50022, DIN EN43880
Position during operation
Free
Mounting
Rail mounting according to DIN35 standard / TS35.
22