7. FACTORY DEFAULT
Parameter
Value
User name
root
Password
dbps
IP Address
Obtain an IP address automatically using DHCP
Operating mode
RealPort
Bout rate[bits/sec]
9600
Number of data bits
8
Parity Control
no
Number of stop bits
1
Flow Control
no
8. TROUBLESHOOTING
Problem
Solution
I forgot the password
Restoring Default Settings according to steps below:
1. Disconnect the power of the converter,
2. Remove the cover of ETHERNET connector,
3. Press RESET “RST” and holding the button, connect the power
of the converter,
4. Release the button after 20 sec. when the converter will start
with default settings.
Restoring Default Settings deletes existing configuration and the
proper configuration should be loaded to the converter from the
backup.
I changed the configuration and the converter isn't functioning.
1. Enter in the Internet browser
2. Select the menu
[Factory Default Settings]
press
[Restore]
.
9. VERSIONS
ADA-13020 -
-
-
-
-
Electronic version:
Basic
1
Current Loop Voltage:
24VDC
1
12VDC
2
Current Loop Type:
± 20mA
1
0 – 20mA (TTY active/passive transmitter, passive
receiver)
2
Galvanic Isolation:
1kV=
2
3kV=
3
Terminal & Terminal Cover:
Cover without inlets, screw terminal block,
1
Cover with inlets, screw terminal block,
2
Cover without inlets, plug-in screw terminal block,
3
25
ADA-13020