Fig 3. Digram of Current Loop transmitter & receiver in ADA-13020

2.5. ISOLATION

The ADA-13020 converter has 3-way, 1kV= or 3kV= galvanic isolation, depend on version described in section 

VERSIONS

Fig 4. Isolation diagram

3. INSTALLATION

This chapter will show how correctly connect ADA-13020 to devices with Current Loop interface, LAN/WAN network and power supply.

To reduce disturbance from environment, it is recommended to:

– use shielded twisted multipair type cables, which shield should be connected to the grounding on one end of the cable,

– lay signal cables at a distance not less than 25 cm from power cables,

– use suitable diameter cable for power supply on account of voltage drop,

– use the interference eliminators for powering the converters installed in the range of some building,

– not powering the converters form power-circuit of devices generate large impulse disturbance like contactors, relays, inverters.

3.1. ASSEMBLING 

The ADA-13020 converter case is adapted to assembly on TS-35 (DIN35) rail. To install the device on TS-35 should be the upper part

of the casing put hooks on the terminal and then press the bottom of the cover until you hear a characteristic "Click" sound.

3.2. ETHERNET NETWORK CONNECTION

The ADA-13020 has to be connected to ETHERNET network by the use of the switch, the HUB or directly to the PC network adapter. 

The table below shows preparing of the straight cable for converter connection to switch or hub.

Table 1.

RJ45 Pin No.

Signal

Wire Color

EIA/TIA 568B

Straight cable

UTP 4x2x0,5

Wire Color

EIA/TIA 568B

Signal 

RJ45 Pin No.

1

TX+

White-Orange

2

TX-

Orange

3

RX+

White-Green

4

Not used

Blue

5

Not used

White-Blue

6

RX-

Green

7

Not used

White-Brown

8

Not used

Brown

White-Orange

TX+

1

Orange

TX-

2

White-Green

RX+

3

Blue

Not used

4

White-Blue

Not used

5

Green

RX-

6

White-Brown

Not used

7

Brown

Not used

8

Table below show preparing of crossover cable for converter connection to network adapter of PC or converters together for operating

like point-to-point serial bridge.

7

ADA-13020

Power Supply

10 - 30VDC

ETHERNET

Current Loop

3-WAY ISOLATION

TX-

I= 0 / 20mA
or
I= -20 / +20mA

I

TX+

RX-

R=560

W  

/ R=1000

W

Passive Receiver

RX+*

Active - Transmitter

RX+

TX-

I= 0 / 20mA

TX+

Passive - Transmitter

U=12VDC / U=24VDC

Summary of Contents for ADA-13020

Page 1: ...User manual ADA 13020 ETHERNET to Current Loop Converter 1 io_ada 13020_v1 14_en ADA 13020 Copyright 2001 2017 CEL MAR sp j...

Page 2: ...ORK SETTING 13 5 2 CONFIGURATION AND MANAGEMENT BY THE USE OF INTERNET BROWSER 15 5 2 1 NETWORK SETTING CONFIGURATION 15 5 2 2 SERIAL PORT CONFIGURATION 16 5 2 2 1 SERIAL PORT PROFILE CONFIGURATION OP...

Page 3: ...6 2 REALPORT CONFIGURATION IN WINDOWS XP 23 7 FACTORY DEFAULT 25 8 TROUBLESHOOTING 25 9 VERSIONS 25 10 SPECIFICATION 26 3 ADA 13020...

Page 4: ...network is only after disconnecting the power supply circuit voltage Do not carry out the assembly or dis assembly of the device if it is enabled This may result to short circuit and damage the devic...

Page 5: ...ade on base safety diodes and fuses on each Current Loop lines To Current Loop interface can be connected one device in point to point topology operates in half duplex or full duplex mode This convert...

Page 6: ...CURRENT LOOP TRANSMITTER The Current Loop transmitter at ADA 13020 is made as active on the base power source generate current depend on converter s version 20mA or 0 20mA TTY The transmitter has a sh...

Page 7: ...ll the device on TS 35 should be the upper part of the casing put hooks on the terminal and then press the bottom of the cover until you hear a characteristic Click sound 3 2 ETHERNET NETWORK CONNECTI...

Page 8: ...OF PC If there is not the switch or the HUB it is possible to connect the ADA 13020 directly to a network adapter of PC using the cross over cable Table 2 This connection can be used for converter co...

Page 9: ...8 Connecting for functioning in TCP UDP serial bridge mode one to one in LAN network 9 ADA 13020 ROUTER Public IP address ETHERNET Straight cable Tabela 1 ETHERNET Straight cable Tabela 1 Current Loop...

Page 10: ...device with active transmitter passive receiver 10 ADA 13020 Current Loop Current Loop Current Loop ADA 13020 Static IP address SLAVE Device with Device with Current Loop interface interface ADA 1302...

Page 11: ...the Current Loop BUS like on the picture below In this case Current Loop bus is created by eg one converter ADA 13020 1 1 2 2 3 MASTER Active Transmitter one converter ADA 1020 1 1 2 2 3 SLAVE Active...

Page 12: ...otection from opposite connection power supply 12 ADA 13020 SLAVE 2 RS232 SLAVE 15 RS232 ADA 1020 1 2 2 3 SLAVE PASSIVE 1 SLAVE 1 RS232 RS232 Rx Rx Rx Tx Tx DB 9F RS232 connector Rx Rx Rx Tx Tx DB 9F...

Page 13: ...AWiz are available in Start Programs CEL MAR ADANet 5 1 2 NETWORK SETTING The ADAFinder is use for configuration of converter s network setting Before running the ADAFinder should be disabled the Syst...

Page 14: ...Fig 14 Basic network configuration Fig 15 IP address setting 14 ADA 13020...

Page 15: ...ow Fig 16 Page for manage and configuration of ADA 13020 converter 5 2 1 NETWORK SETTING CONFIGURATION To make changes of default setting or new configuration of ADA 13020 select on left panel Configu...

Page 16: ...erial Port Configuration select Port 1 will open the configuration details page includes Port Profile Settings Basic Serial Settings Advanced Serial Settings 5 2 2 1 SERIAL PORT PROFILE CONFIGURATION...

Page 17: ...5 2 2 1 2 TCP SOCKETS CONFIGURATION Choosing TCP Sockets is configured the serial port of ADA 13020 for direct communication with PC by the use of TCP socked Data sending by application to TCP socked...

Page 18: ...e is 2101 If on the local network is conflict with other network service using the same port in the converter s port configuration change number of port into another for the server and client service...

Page 19: ...ofile will open section UDP Server Settings with operating parameters like on picture below Set access to UDP server on e g 2101 port Then select Automatically send serial data in section UDP Client S...

Page 20: ...working UDP Server of converter connected to MASTER device and press Add In the section Send data under any of the following conditions is recommended to set parameters like on picture bellow For sav...

Page 21: ...ts Parity Stop Bits the same parameter like has device connected to the serial port of the converter 5 2 3 SYSTEM SETTINGS Select on left panel menu Configuration System and then on right will be sele...

Page 22: ...tore the factory default settings to display system details information to reboot the converter 5 2 6 1 FILE MANAGEMENT Section File Management enables upload and delete Web provided by manufacturer U...

Page 23: ...Open 6 when the installation window will appear press Next 7 will start the searching for converters in the network 8 if no devices were not found press Next 9 should be set in the window Describe the...

Page 24: ...Fig 24 Device view on Windows XP Fig 25 Example configuration of multi port serial adapter 24 ADA 13020...

Page 25: ...ec when the converter will start with default settings Restoring Default Settings deletes existing configuration and the proper configuration should be loaded to the converter from the backup I change...

Page 26: ...nalization PWD green LED power supply RX red LED data reception on Current Loop port TX yellow LED data transmission via Current Loop port Electrical Parameters Power requirements 10 24 30 V DC Power...

Page 27: ...27 ADA 13020...

Page 28: ...a transmission converters with interface RS232 RS485 RS422 USB Current Loop Fibre Optic Converters and Ethernet or Wi Fi Please contact us to tell how you like our products and how we can satisfy you...

Reviews: