– terminal mode,
– modem emulation mode,
– console mode,
– user mode.
However, in the case of the Current Loop converter, it will not be able to work properly in these modes, as they relate to the full RS232
interface.
2.4. CURRENT LOOP INTERFACE
2.4.1. CURRENT LOOP TRANSMITTER
The Current Loop transmitter in the ADA-13021 was made as a passive 0-20mA(TTY), having low energy short circuit protection on
TX+ and TX- lines. By the correct connection of the transmitter with power source I1, Current Loop transmitter 0-20mA can operate as
active. The transmitter diagram is shown on figure below.
2.4.2. CURRENT LOOP RECEIVER
The ADA-13021 converter has passive RX receiver having low energy short circuit protection on TX+ and TX- lines.
By the correct connection of the receiver with power source I2, Current Loop receiver 0-20mA can operate as active.
The receiver has signalization of non current flow through optocoupler. It is indicated by the red LED RX on front panel of the
converter. This LED lit when it is:
- not connect transmitter to receiver,
- wrong connection of transmitter to receiver,
- broken connection of transmitter to receiver.
The diagram is shown on figure below.
Fig. 3. Diagram of the transmitter & receiver ADA-13021 Current Loop
2.5. ISOLATION
Converter ADA-13021 has 3-way galvanic isolation on level 1kV= or 3kV=, depend on version described in section
VERSIONS
.
Fig. 4. Isolation structure
3. INSTALLATION
This chapter will show how to connect ADA-13021 to Current Loop bus, LAN/WAN network and power supply and how to use it.
In the purpose of minimization of disruptions from environment is being recommended to:
●
apply multipair type shielded cables, which shield can be connected to the earthing on one end of the cable,
●
arrange signal cables in the distance not shorter than 25 cm from powering cables,
●
apply cable of adequate cross-section due to voltage drops for converter powering,
●
use Interference suppression filters for power supply converters that are installed within a single object.
●
not supply converter from power circuit device that generates large impulse interference such as transmitters, contactors,
6
ADA-13021
Power Supply
10 - 30VDC
ETHERNET
Current Loop
3-WAY ISOLATION
I2 -
I= 0 / 20mA
I
I2 +
RX-
Passive Receiver
I2 – Receiver's
Current source
RX+
TX-
I= 0 / 20mA
TX+
Passive Transmitter
I1 -
I= 0 / 20mA
I
I1 +
I1 – Transmitter's
Current source
Summary of Contents for ADA-13021
Page 26: ...26 ADA 13021...
Page 27: ...27 ADA 13021...