Fig. 26. Example configuration for communication with MODBUS-MASTER devices – Modbus RTU setting
Then select section
Slave Destinations (Packet Routing)
– figure below.
In this section press
[Add],
enter the IP address of
Slave
type devices, to which
Master
will send requests and receive responses.
Fig. 27. Example configuration for communication with MODBUS-MASTER devices – table configuration of SLAVE type
devices
In section
Destination Settings
(fig. below) set the options of requests from
Master
device to
Slave
device, in fields:
–
Host name
- enter IP address of
Slave
device.
–
Protocol
- set protocol which will be send to
Slave
device – in this case will be Modbus/TCP.
–
Transport
- set TCP protocol .
–
Network port
- set port 502.
Press [
Apply
] for saving configuration. Then press again
[Add]
for adding another
Slave
device.
Then select section
Slave Destinations (Packet Routing)
, when all
Slave
devices are added and set, press
[Apply].
23
ADA-13021MG