Fig. 28. Example configuration for communication with MODBUS-MASTER devices – table entry configuration for SLAVE type
devices
On section
Advanced Protocol Settings
(fig. below), set the time out by entry:
–
Character timeout
- value in ms., maximum delay or gap betweens bytes of a message – default 20 ms.
–
Message timeout
- value in ms., maximum delay or gap betweens bytes of a message – default 2500ms; this time must be less
than the Timeout set on SLAVE and MASTER MODBUS-RTU devices.
For saving the
Advanced Protocol Settings
press [
Apply
].
Fig. 29. Example configuration for communication with MODBUS-MASTER devices – configuration of timeout parameters for
MASTER type device
24
ADA-13021MG