5.3.2.1.3.2. UDP CLIENT & SERVER CONFIGURATION IN CASE OF SLAVE DEVICE
Set operating parameters of UDP server for SLAVE device connected via serial port to ADA-13040MG, eg like on picture below. Set
an access to UDP server on e.g. 2101 port. Then select
Automatically send serial data
in section
UDP Client Settings
, this
automatically send received data by the use UDP client service to t he MASTER device connected to LAN / WAN through e.g.
ADA-13020, ADA-13028L, ADA-13040MG, ADA-13110, ADA14040, ADA-14040.
On lists
Send data to the following network services
are addresses of network devices and ports to which will be send data. In
field:
-
Description
- enter e.g. location of the converter and MASTER device,
-
Send To
- enter IP address of e.g. converter, connected to MASTER device,
-
UDP Port
- enter the number of port on which is working UDP Server of converter connected to MASTER device and press
[Add]
In the section
Send data under any of the following conditions
is recommended to set parameters like on picture bellow.
For saving the configuration of UDP client and server for SLAVE device, press
[Apply]
.
Fig 20. Example configuration of the UDP server&client on converter connected to SLAVE device
Attention !
Default port of serial port service is 2101.
If on the local network conflict with other network service using the same port, change number of port into another for the
service server of serial bridge and client in the server port configuration.
5.3.2.1.3.3. SERIAL PORT TRANSMISSION PARAMETERS
For proper operation of ADA-13040MG with device connected to his RS485/RS422 serial port, should be set the same transmission
parameters for both devices.
Select
Basic Serial Settings
and enter
Baud Rate
,
Data Bits
,
Parity
,
Stop Bits,
the same parameter like has device connected to
the Wireless Serial Server.
5.3.2.1.4. SERIAL BRIDGE
Choosing the
Serial Bridge
profile enable direct communication between two devices connected to two ADA-13040MG converters
over the network as if they were connected with a serial cable. A properly configured ADA-13040MG will start automatically
communication with each other.