5.3.2.1.5.1. COMMUNICATION WITH DEVICES MODBUS-MASTER TYPE
In section
Industrial Automation Settings
, press
[Change Protocol]
link. Then in section
Select IA Protocol
(figure below) select
type of device, connected to serial port of ADA-13040MG, as
Serial Master
and MODBUS-RTU or MODBUS-ASCII protocol for
communication between connected devices. Press
[Apply]
for saving configuration.
Fig 23. Example configuration for communication with MODBUS-MASTER devices
Set the options in section
Modbus RTU Settings
like on Fig.22 and press
[Apply].
Then select section
Slave Destinations (Packet Routing)
– fig below; and press
[Add].
Section
Destination Settings
will open.
Fig 24. Example configuration for communication with MODBUS-MASTER devices – type of device and protocol
In section
Destination Settings
(fig. below) set the options of inquires from
Master
device to
Slave
device, in fields:
- Host name
- enter IP address of
Slave
device.
- Protocol
- set protocol which will be send to
Slave
device – in this case will be Modbus/TCP.
- Transport
- set TCP protocol .
- Network port
- set port 502.
Press [
Apply
] for saving. Then press again
[Add]
for adding another
Slave
device.
When all Slave devices are added and set press
[Apply].