Fig 25. Example configuration for communication with MODBUS-MASTER devices - type of devices and protocol
Next section is
Advanced Protocol Settings
(fig. below), set the time outs :
- Character timeout
- value in ms., maximum delay or gap betweens bytes of a message – default 20 ms.
- Message timeout
- value in ms., maximum delay or gap betweens bytes of a message – default 2500ms; this time must be
less than the Timeouts set on SLAVE and MASTER MODBUS-RTU devices.
For saving the
Advanced Protocol Settings
press [
Apply
].
Fig 26. Example configuration for communication with MODBUS-MASTER devices – setting of Timeouts
21
ADA-13040MG