5.3.2.1.5.2. CONFIGURATION FOR COMMUNICATION WITH MODBUS-SLAVE TYPE
DEVICE
In section
Industrial Automation Settings
, press
[Change Protocol]
link. Then in section
Select IA Protocol
(figure 23) select
type of device, connected to serial port of ADA-13040MG, as
Serial Slave
and MODBUS-RTU or MODBUS-ASCII protocol for
communication between connected devices. Press
[Apply]
for saving configuration.
In section
Modbus RTU Settings
set option e.g. as figure below and press
[Apply].
Fig 27. Example configuration for communication with MODBUS-SLAVE
Select section
Modbus/TCP Network Settings [Global],
and
set option e.g. as figure below and press
[Apply].
Fig 28. Example configuration for communication with MODBUS-SLAVE
Attention !
Default port of Industrial Automation (Modbus Gateway) is 502.
If on the local network conflict with other network service using the same port, change number of port into another for the
service server of serial bridge and client in the server port configuration.
5.3.2.1.5.3. SERIAL PORT TRANSMISSION PARAMETERS
For proper operation of ADA-13040MG with device connected to his RS485/RS422 serial port, should be set the same transmission
parameters for both devices.
Select
Basic Serial Settings
and enter
Baud Rate
,
Data Bits
,
Parity
,
Stop Bits,
the same parameter like has device connected to
the Wireless Serial Server.
22
ADA-13040MG