2.4. ISOLATION

Converter ADA-4010  has 2-way or 3-way galvanic isolation on the levels 1kV= or 3kV=, depend on version described in section
VERSIONS.

Fig 2. Isolation structure

3. INSTALLATION

This chapter will show how to use and connect ADA-4010 to PC, RS485, RS422 network and power supply.
In the purpose of minimization of disruptions from environment is being recommended to:
- apply multipair type shielded cables, which shield can be connected to the earthing on one end of the cable,
- arrange signal cables in the distance not shorter than 25 cm from powering cables.
- apply cable of adequate cross-section due to voltage drops for converter powering,
- use suppression filters for powering converters that are installed within a single object.
- not supply converter from power circuit device that generates large impulse interference such as transmitters, contactors.

3.1. ASSEMBLING

ADA-4010 converter case is adapted to assembly on TS-35 (DIN35) rail. To install converter should mount device on the rail upper
part of the case then press bottom part to hearing characteristic „Click” sound.

3.2. COMPUTER CONNECTION

In purpose of connecting ADA-4010 to computer, should be used:
- to RS232 computer's port, should be use a cable according to the fig.3.
- to USB computer's port, should be use additional converter USB to RS232 – ADA-I9111 or ADA-I9110, connected to RS232 ADA-
4010 port like on the fig.4.

Fig. 3. ADA-4010 connection to PC by the use of cable

Fig. 4. ADA-4010 connection to PC by the use of USB to RS232 converter ADA-I9110/ADA-I9111

5

ADA-4010

(5) GND

(2) Rx

(3) Tx

DB-9M RS232 

connector

GND

RS485/422 
Connector

Tx+ / A

Tx- / B

Rx+

Rx-

RS232 

Connector

ADA-4010

.

   

Tx

Rx

.

GND

DB-9F
socket

(5)

(2)
(3)

Computer

Computer

.

USB

USB

 Connector

ADA-I9110

USB

(5) GND

.

(2) Rx

(3) Tx

Tx+ / A

Tx- / B

Rx+

Rx-

ADA-4010

(5)

(2)
(3)

.

   

Tx

Rx

.

GND

RS485/422 
Connector

RS232 

Connector

DB-9M RS232 

connector

DB-9F
socket

USB

 Connector

Power Supply

10 - 30VDC

RS485

RS232

3-WAY ISOLATION

Power Supply

10 - 30VDC

RS232

RS485

2-WAY ISOLATION

Summary of Contents for ADA-4010

Page 1: ...User manual ADA 4010 RS 485 RS 422 to RS 232 Converter 1 io_ada 4010_v3 23_en ADA 4010 Copyright 2001 2020 CEL MAR sp j...

Page 2: ...ION 5 3 INSTALLATION 5 3 1 ASSEMBLING 5 3 2 COMPUTER CONNECTION 5 3 1 CONNECTION TO RS485 RS422 BUS 6 3 1 1 CONNECTION TO RS422 BUS 6 3 1 2 CONNECTION TO RS485 4W BUS 6 3 1 3 CONNECTION TO RS485 2W BU...

Page 3: ...on device sources candles an oil lamps and the like Complete disable from the supply network is only after disconnecting the power supply circuit voltage Do not carry out the assembly or dis assembly...

Page 4: ...voltage protection was made on base safety diodes and fuses on each RS485 RS422 lines To RS485 RS422 bus created on the base ADA 4010 converters can be connected up to 32 devices operating in mode hal...

Page 5: ...10 converter case is adapted to assembly on TS 35 DIN35 rail To install converter should mount device on the rail upper part of the case then press bottom part to hearing characteristic Click sound 3...

Page 6: ...device 6 ADA 4010 5 GND 2 Rx 3 Tx RS232 DB 9M connector PC GND RS422 connector Tx Tx Rx Rx Device with RS422 interface DB 9F socket 5 2 3 GND RS485 RS422 connector Tx A Tx B Rx Rx RS232 connector ADA...

Page 7: ...g 6 7 Two Rt 120 W 5 0 25W are delivered with the converters 3 1 6 CONNECTION OF RS232 DEVICE Example connection of SLAVE device with RS232 interface to ADA 4010 are shown on Fig 6 7 3 2 POWER SUPPLY...

Page 8: ...W1 1 SW1 2 SW1 3 SW1 4 SW1 5 SW1 6 ON ON ON ON ON ON 5 ACTIVATION After properly connection according to section above the converter can be powered If the power is properly connected on the front pane...

Page 9: ...ver without inlets plug in screw terminal block Electronic versions Basic 1 Special 2 Galvanic isolation 1kV 2 way 2 1kV 3 way 23 3kV 2 way 3 3kV 3 way 33 Terminal Terminal Cover Cover without inlets...

Page 10: ...ower requirements 10 24 30 V DC Power Cable Recommended length of power cable do 3m Power 2W Protection from reverse power polarization YES Galvanic Isolation 1kVDC or 3kVDC between power circuit and...

Page 11: ...11 ADA 4010...

Page 12: ...ransmission converters with interface RS232 RS485 RS422 USB Ethernet Wi Fi Current Loop Fibre Optic Converters and other Please contact us to tell how you like our products and how we can satisfy you...

Reviews: