3.3.1. LINE TERMINATION
The application of Line Termination (terminator) Rt = 120
W (
ohms) will reduce electrical reflection in data line at high baud rate. It is
not needed below 9600Bd. The Line Termination resistor should be used if the distance is over 1000m @ 9600Bd or 700m @
19200Bd transmission, the resistor can be necessary if there are problems with the transmission correctness. Example connection of
Rt to screw terminal block of RS485/422 interface ADA-401WA are shown on Fig. 6 & 7.
3.4. CONNECTION TO 1-WIRE NETWORK
3.4.1. CONNECTION 1-WIRE SENSORS
Way to link temperature sensor to ADA-401WA converter is shown on figure below.
Fig. 8. Sensor connection to ADA-401WA converter by 3-wire 1-WIRE Bus
Fig. 9. Sensor connection to ADA-401WA converter by 2-wire 1-WIRE Bus
3.4.2. LIMITATIONS OF 1-WIRE BUS
The maximum length of 1-wire bus as layouts producer can be even 400m and the maximum number of sensors can be 500.
However, when building the bus, remember that, each sensor is a shortening of 0,5 meters and 100 meters of cable causes additional
capacity load data line 5nF increasing signal distortion.
1-WIRE bus length and number of sensors will be less and will depend on:
–
used cables,
–
topology connection,
–
quality implementation of connections,
–
interference from external electromagnetic fields.
RECOMMENDS:
–
application of twisted cables UTP 4x2x0,5,
–
powered converter with an individual power supply with good parameters, eg. DR-15-24,
–
linear topology of 1-WIRE bus (sensors in a star topology can be converted to linear topology by using Passive 1-WIRE
Bus Splitter ADA-DNB400),
–
finishing 1-WIRE bus by sensor,
–
connecting unused wires and screen cable to rail EP of electrical installation.
7
ADA-401WA
V+
1-WIRE (3W) Bus
ADA-401WA
VDD
GND
1-W
Rx+
10–30 VDC
3W
Tx+/ A
Tx-/ B
GND
Rx-
Power
Supply
V -
V +
V-
DS18B20
Sensor
1-WIRE
connector
RS485/422
connector
DS18B20
Sensor
DS18B20
Sensor
ADA-401WA
VDD
GND
1-W
Rx+
Tx+/ A
Tx-/ B
GND
Rx-
V -
V +
V+
10–30 VDC
3W
V-
1-WIRE (3W) Bus
DS18B20
Sensor
1-WIRE
connector
RS485/422
connector
DS18B20
Sensor
DS18B20
Sensor
Power
Supply