background image

3.3.2. CONNECTION TO RS485 (2-WIRES) BUS

Fig 7. Example connection of ADA-4020A to RS485 2-wires bus and galvanic separation of SLAVE device.

3.3.3. GND TERMINALS CONNECTION

Connection of GND terminals of RS485/422 interfaces, devices connected to RS485/422 bus, should be done in the case of a 

potential difference of the signals grounds on interfaces RS485 / RS422, which prevents proper data transmission.

Cannot connect to the GND terminal - cables screens, PE circuit of electrical installation, signals grounds of other devices.

3.3.4. LINE TERMINATION

The application of Line Termination (terminator) Rt = 120 ohms will reduce electrical reflection in data line at high baud rate. It is not

needed below 9600Bd. The Line Termination resistor should be used if the distance is over 1000m @ 9600Bd or 700m @ 19200Bd

transmission, the resistor can be necessary if there are problems with the transmission correctness. Example connection of Rt are
shown on Fig. 6 & 7. Resistor Rt = 120 

W

, 5%, 0.25W of a 2 pc. is complete with the device ADA-4020A.

3.3.5. CONNECTION OF CURRENT LOOP DEVICES

The connections of SLAVE devices with current loop interface to ADA-4020A are shown on Fig.6 & Fig.7.

3.4. POWER SUPPLY

The power supply to ADA-4020A should be DC (regulated) from the scope 10 V= to 30V= and nominal power more then 2W. The

power cable from DC power supplies to the device must not be longer than 3m. Observe the polarity, connect positive (+) of DC power

supplies to V+ and negative (-) end to V- terminal. The ADA-4020A has the protection from opposite connection power supply.

If after power, on the front panel is not lit green LED PWR, check the power connection (polarity).

4. ACTIVATION

Converter can be powered after proper connection according to steps above. 

If   connection   was   made   properly   green   LED   PWR   on   front   panel   of   converter   should   light,   if   not   check   polarization   of   power

connection and if RX LED is lighted check connection correctness of Current Loop CLO transmitter circuit. Lighting this LED indicates

non flow of current through optocoupler in receiver circuit.

During correctness data transition via the converter the LEDs Tx and Rx should blinking.

7

ADA-4020A

(5) GND

GND

(2) Rx

(3) Tx

ADA-I1040

GND (5)

Tx (2)

Rx (3)

Rt

Rx+

Rx-

Tx+/ A

Tx-/ B

RS485(4W) bus
9600Bd/8/O/1

PC or

MASTER device

CL

SLAVE
2400Bd/8/N/2

SLAVE
19200/Bd/7/N/2

SLAVE
9600Bd/8/E/1

CL

CL

RS232 

connector 

DB-9F/DCE

RS485 / RS422

connector

RS232 

connector

DB-9M/DTE

Summary of Contents for ADA-4020A

Page 1: ...User manual ADA 4020A Addressable RS485 422 to Current Loop Baud Rate Converter 1 io_ada 4020a_en v 4 02 ADA 4020A Copyright 2001 2017 CEL MAR sp j...

Page 2: ...TO RS485 2 WIRES BUS 7 3 3 3 GND TERMINALS CONNECTION 7 3 3 4 LINE TERMINATION 7 3 3 5 CONNECTION OF CURRENT LOOP DEVICES 7 3 4 POWER SUPPLY 7 4 ACTIVATION 7 4 1 SIGNALING LEDS 8 5 CONFIGURATION 8 5 1...

Page 3: ...the assembly or dis assembly of the device if it is enabled This may result to short circuit and damage the device The device can not be used for applications that determine human life and health eg...

Page 4: ...baud rate up to 230 4 kbps via one or two pairs of twisted pair cables of RS485 422 interface and up to 38 4 kbps on 4 wires Current Loop bus ADA 4020A is equipped with screw terminal block for conne...

Page 5: ...connection of transmitter to receiver Review diagram of the receiver is shown on figure below Fig 2 Review diagram of the transmitter receiver Current Loop ADA 4020A Converter 2 5 ISOLATION Converter...

Page 6: ...as Tx A Tx B Rx Rx Below are shown connection of ADA 4020A converter to RS485 4W bus and RS485 2W bus 3 3 1 CONNECTION TO RS485 4 WIRES BUS Fig 6 Example connection of ADA 4020A to RS485 4 wires bus a...

Page 7: ...th current loop interface to ADA 4020A are shown on Fig 6 Fig 7 3 4 POWER SUPPLY The power supply to ADA 4020A should be DC regulated from the scope 10 V to 30V and nominal power more then 2W The powe...

Page 8: ...ly If after power on the front panel is not lit green LED PWR check the power connection polarity If the PWR LED lights set the section of SW1 switch to configuration mode as in table below SW1 1 SW1...

Page 9: ...ace operates in receiving transmitting data mode for RS485 bus 2 wires and 4 wires signal DE On RS485 RS422 interface operates in RS422 mode After configuration the setting should be saved on converte...

Page 10: ...as shown in the table below SW1 1 SW1 2 OFF OFF Yellow LED will be OFF 5 4 EMERGENCY FIRMWARE UPDATE In case of the unsuccessful update of the converter software try again according to description in...

Page 11: ...A 4020A converter s configuration and correctness connection of RS485 bus and Current Loop device to the converter ports After finishing the diagnostics the SW1 micro switch should be set to standard...

Page 12: ...duplex mode on RS 422 and RS 485 4 wire bus Additionally can be set data flow control for RS485 RS422 interface according to pt CONFIGURATION BY THE USE OF ADACONFIG On a picture below are shown the...

Page 13: ...ferences STP Nx2x0 5 24AWG 2 pair twisted cable UTP Nx2x0 5 24AWG shield inside large interferences STP Nx2x0 5 24AWG Transmission type Asynchronism full duplex half duplex Standards EIA 232 CCITT V 2...

Page 14: ...ryl UL 94 V O Degree of casing protection IP40 Degree of terminal protection IP20 Weight 0 10 kg According to standard DIN EN50022 DIN EN43880 Position during operation Free Mounting Rail mounting acc...

Page 15: ...15 ADA 4020A...

Page 16: ...transmission converters with interface RS232 RS485 RS422 USB Ethernet Wi Fi Current Loop Fibre Optic Converters and other Please contact us to tell how you like our products and how we can satisfy you...

Reviews: