3.3.2. RS485(2W) BUS CONNECTION

Fig 7. Example connection of ADA-4040PC1 to RS485(2W) 2-wire bus and galvanic separation of SLAVE device

3.3.3. GND TERMINALS CONNECTION

Connection of GND terminals of RS485/422 interfaces, devices connected to RS485/422 bus, should be done in the case of a 

potential difference of the signals grounds on interfaces RS485 / RS422, which prevents proper data transmission.

Cannot connect to the GND terminal - cables screens, PE circuit of electrical installation, signals grounds of other devices.

3.3.4. LINE TERMINATION Rt

The application of Line Termination (terminator) Rt = 120 ohms will reduce electrical reflection in data line at high baud rate. It is not

needed below 9600Bd. Should be used the Line Termination resistor if the distance is over 1000m @ 9600Bd or 700m @ 19200Bd,

and if the disturbance in transmission will appear.
Example connection of Rt are shown on Fig. 6 & 7. Four Rt=120 

, 5%, 0,25W are delivered with the converters.

3.3.5. SLAVE DEVICE CONNECTION

Connection of SLAVE devices to ADA-4040PC1 are shown on fig. 5 and fig. 6.

3.4.  POWER SUPPLY CONNECTION

To connect power supply to the converter, should have DC power supplies (regulated) output voltage from 10 V= to 30V=, min.

nominal power 2W, e.g. ZS-12/250. Power cable from DC power supplies to device can not be longer than 3m. Should connect

positive (+) end of DC power supplies to V+ device terminal and negative (-) end to V- on terminal block. ADA-4040PC1 has protection

against power supply reverse connection.

4. ACIVATION

The converter Can be power on after properly connection according to section above.

If   after   connection   power   supply   on   front   panel   will   not   light   green   led   PWR,   check   correctness   of   power   supply   connecting

(polarization). When data is present the LEDs Tx and Rx should blink

7

ADA-4040PC1

GND

RS485 (2W) bus
9600Bd/8/N/1
MODBUS-RTU

Rt

Rx+

Rx-

Tx+/ A

Tx-/ B

SLAVE-2
MODBUS-RTU

Tx+/ A

Tx-/ B

   

Rx+

Rx-

Rt

Rt

SLAVE-1
MODBUS-RTU

GND

Rt

Rt

Rx+

Rx-

Tx+/ A

Tx-/ B

SLAVE-3
MODBUS-ASCII

GND

Rt

Rx+

Rx-

Tx+/ A

Tx-/ B

Tx+/ A

Tx-/ B

   

Rx+

Rx-

Rt

Rt

GND

Rt

Rt

Rx+

Rx-

Tx+/ A

Tx-/ B

MASTER

MODBUS-ASCII

DEVICE

GND

RS485(2W)
19200/Bd/7/N/2

RS485 / RS422

connector

ASCII

RS485/RS422

connector

RTU

RS485/RS422

connector

ADA-4040PC1

MODBUS-ASCII / MODBUS-RTU

Summary of Contents for ADA-4040PC1

Page 1: ...User manual ADA 4040PC1 MODBUS ASCII to MODBUS RTU converter 1 io_ada 4040pc1_v1 03_en ADA 4040PC1 Copyright 2001 2017 CEL MAR sp j...

Page 2: ...485 NETWORK CONNECTION 6 3 3 1 RS485 4W BUS CONNECTION 6 3 3 2 RS485 2W BUS CONNECTION 7 3 3 3 GND TERMINALS CONNECTION 7 3 3 4 LINE TERMINATION Rt 7 3 3 5 SLAVE DEVICE CONNECTION 7 3 4 POWER SUPPLY C...

Page 3: ...twork is only after disconnecting the power supply circuit voltage Do not carry out the assembly or disassembly of the device if it is enabled This may result to short circuit and damage the device Th...

Page 4: ...on RS422 485 bus and increases its reliability ADA 4040PC supports the asynchronous baud rate up to 230 4 kbps through four or two pairs of twisted pair cables connected to screw terminals The convert...

Page 5: ...nverter should be mounted on the rail upper part of the cover then press bottom part to hear characteristic Click sound 3 2 COMPUTER CONNECTION To connect ADA 4040PC1 to computer equipped with RS 232...

Page 6: ...separation of SLAVE device 6 ADA 4040PC1 GND USB PC USB Rx Rx Tx A Tx B Tx A Tx B Rx Rx Tx A Tx B GND Rx Rx GND ADA I9140 ADA 4040PC1 USB connector RS485 RS422 connector USB connector RTU RS485 RS422...

Page 7: ...of SLAVE devices to ADA 4040PC1 are shown on fig 5 and fig 6 3 4 POWER SUPPLY CONNECTION To connect power supply to the converter should have DC power supplies regulated output voltage from 10 V to 30...

Page 8: ...n modes SW1 1 SW1 2 Mode OFF OFF Run ON OFF Configuration OFF ON Factory default Turning OFF and ON the power of the converter the configuration will be set to factory default ON ON Emergency firmware...

Page 9: ...d New Firmware to change the software delivered by manufacturer The Select File window will open fig below and select the bin file then click Open software will be load to ADAConfig buffer storage and...

Page 10: ...After microswitch setting should be restarted ADA 4040PC1 by turning OFF and then ON the power supply The yellow LED will light continuously and the converter will be in Emergency Firmware Update mod...

Page 11: ...n case of misrepresent bytes in transmitted sign This counter will not work in case of disable control parity To check those counters press the button Read transmission errors and to delete zeroing of...

Page 12: ...ds on baud rate Max number of connected device Up to 32 devices Baud rates bps 300 600 1200 1800 2400 4800 7200 9600 14400 19200 28800 38400 57600 76800 115200 230400 Data formats Data bits 5 6 7 8 Pa...

Page 13: ...5 RS 422 ASCII and RS 485 RS 422 RTU Electromagnetic compatibility Resistance to disruptions according to the standard PN EN 55024 Emission of disruptions according to the standard PN EN 55022 Safety...

Page 14: ...14 ADA 4040PC1...

Page 15: ...15 ADA 4040PC1...

Page 16: ...data transmission converters with interface RS232 RS485 RS422 USB Current Loop Fibre Optic Converters and Ethernet or Wi Fi Please contact us to tell how you like our products and how we can satisfy y...

Reviews: