background image

During loading software the yellow LED located beside SW1 micro-switch will blink, showing data flow to the converter. If the software

was loaded correctly yellow LED will be blink again with frequency 1 Hz.

After that, set microswitch SW1 to RUN mode as shown in the table below.

SW1-1 

SW1-2 

OFF 

OFF 

In the RUN mode the yellow LED (located near the SW1), will turn off.

5.4. EMERGENCY FIRMWARE UPDATE 

In case of the unsuccessful update of the converter software, try again according to description in the above point. If the update is still 

incorrect use emergency firmware update. Set SW1 microswitch mode as in the table below.

SW1-1 

SW1-2 

ON 

ON 

After microswitch setting, converter should be restarted, by turning OFF and then ON the power supply. The yellow LED will light 

continuously and the converter will be in Emergency Firmware Update mode. Now follow the description in the above point.

After successful software update, set microswitch SW1 to the RUN mode as shown in the table below.

SW1-1 

SW1-2 

OFF 

OFF 

In the RUN mode the yellow LED (located near the SW1), will turn off.

5.5. FACTORY DEFAULT

In case of faulty functioning of ADA-4040PC8, like:

- no communication in the configuration mode,

- transmission errors on RS485/422 bus,

can be restored the factory default setting of the converter internal registers.

Factory default

Parameter 

JCT 

RS485/RS422 

RTU

RS485/RS422 

Device address

64 

Baud rate

9600 bps 

9600 bps 

Data bits

Parity

None 

None 

Stop bits

Interval between frames in bytes 

Set SW1 microswitch mode as in the table below.

SW1-1 

SW1-2 

OFF 

ON 

Disconnect the power and after while connect again the power. After that, will be loaded the factory default setting to the converter

internal registers.

After this operation, the converter parameters should be set again for operating in the application.

Set micro switch SW1 to run mode as shown in the table below.

SW1-1 

SW1-2 

OFF 

OFF 

In the RUN mode the yellow LED (located near the SW1), will turn off.

6. DATA TRANSMISSION DIAGNOSTICS

To readout diagnostics, the SW1 microswitch should be set to the configuration mode.

SW1-1

SW1-2

ON

OFF

In the configuration mode the yellow LED will blink with frequency 1Hz.
Correctness of transmission proceed on JCT (RS485) and RTU(RS485) interfaces can be checked by readout the errors list by

ADAConfig 

Software from the converter memory. Frames error counter will be increased, in case of: improper speed set compared to

real speed of data transmission. Parity error counter will  be count the errors  which  can arise in case of  misrepresent bytes  in

transmitted sign. This counter will not work in case of disable control parity.

To check those counters press the button  

[Read transmission errors],

  and to delete (zeroing of counters in the memory of the

converter)  press  

[Delete   transmission  errors].  

In  case  of   parity  errors   or  frame  errors,  should   be  checked  the ADA-4040PC8

converter's configuration and correctness connection of RS485 bus to RTU and JCT converter ports.

After finishing the diagnostics, the SW1 microswitch should be set to the run mode as shown in the table below.

SW1-1

SW1-2

OFF

OFF

In the run mode the yellow LED (located near the SW1), will turn off.

10

ADA-4040PC8 

Summary of Contents for ADA-4040PC8

Page 1: ...User manual ADA 4040PC8 VIRAP JCT ASCII to MODBUS RTU Protocol Converter 1 ADA 4040PC8 Copyright 2001 2021 CEL MAR io_ada 4040pc8_v1 02_en...

Page 2: ...ING 7 5 CONFIGURATION 7 5 1 OPERATION MODE 7 5 2 CONFIGURATION BY USING ADACONFIG 8 5 3 FIRMWARE UPDATE 9 5 4 EMERGENCY FIRMWARE UPDATE 10 5 5 FACTORY DEFAULT 10 6 DATA TRANSMISSION DIAGNOSTICS 10 7 O...

Page 3: ...the power supply circuit voltage Do not carry out the assembly or disassembly of the device if it is enabled This may result to short circuit and damage the device The device can not be used for appli...

Page 4: ...reliability ADA 4040PC8 supports asynchronous data transmission with baudrate up to 230 4 kbps through two or one pair of twisted pairs connected to screw terminals The device for its operation uses...

Page 5: ...e the rail upper part of the cover then press bottom part it hear characteristic Click sound 3 2 COMPUTER CONNECTION To connect ADA 4040PC8 to computer is needed additional converter e g ADA I9141 USB...

Page 6: ...bus and JCT1 controller to ADA 4040PC8 6 ADA 4040PC8 RS485 RS422 connector RS485 4W BUS 19200Bd 8 N 1 MODBUS RTU MASTER MODBUS RTU DEVICE SLAVE 1 MODBUS RTU GND Rt Rt Rx Rx Tx A Tx B RS485 2W 9600Bd 8...

Page 7: ...the LEDs Tx and Rx should blink ATTENTION AT BAUD RATE ABOVE 38 4 KBPS OF THE TX DIODE MORE POORLY WILL LIGHT RX DURING THE DATA TRANSFER 4 1 DESCRIPTION OF SIGNALLING LEDS LED Description PWR Signal...

Page 8: ...nd in the field Address enter the MODBUS RTU converter address from the RTU port 4 setting the address of the connected VIRAP JCT device to the JTC RS485 port Mapped Address field range 1 99 In the se...

Page 9: ...e the software delivered by manufacturer The Select File window will open fig below and select the bin file then click Open software will be load to ADAConfig buffer storage and will be checked If the...

Page 10: ...tes 4 4 Set SW1 microswitch mode as in the table below SW1 1 SW1 2 OFF ON Disconnect the power and after while connect again the power After that will be loaded the factory default setting to the conv...

Page 11: ...IMPLEMENTATION OF THE MODBUS RTU PROTOCOL MODBUS protocol frames with the CRC error are rejected by the converter JCT ASCII protocol frames with a checksum error are rejected by the converter In case...

Page 12: ...000 0 2000 1000 EV Event value 15 30135 Read 0 1 0 1 1 CM Communication mode 16 30136 Read 0 1 0 1 1 AM Automatic manual mode 17 30137 Read 0 1 0 1 1 SR Execution stop mode 18 30138 No Read 0 100 0 1...

Page 13: ...saved to regular type variable float and then divide it by the DW factor Fragment of code in C language VS6 0 presenting above algorithm short int siMeasureReg float fMeasureVal fMeasureVal float siMe...

Page 14: ...ave values to 16 bits of the MODBUS register of the ADA 4040PC8 converter The saved value in the register is processed and transmitted to the JCT controller MODBUS registers are in the format of the 1...

Page 15: ...1 Byte 40 01 to F7 01 Code of the function 1 Byte 86 02 Error code 1 Byte 01 unknown function 02 unknown data address 03 unknown amount of data 04 JCT controller is not responding is not connected or...

Page 16: ...ate from RTU of ports RS485 RS422 TX yellow LED date transmission through RTU of ports RS485 RS422 Electrical Parameters Power requirements 10 24 30 V DC Power Cable Recommended length of power cable...

Page 17: ...data transmission converters with interface RS232 RS485 RS422 USB Current Loop Fibre Optic Converters and Ethernet or Wi Fi Please contact us to tell how you like our products and how we can satisfy y...

Reviews: