Fig. 6. Example connection of ADA-7040 converters by the use of Fibre-Optic line.

3.4. POWER SUPPLY CONNECTION

The power supply to the ADA-7040 converter should be DC (regulated) from 10 V= to 30V=. Nominal power is typically 2W, e.g. ZS-

12/250 or DR-15-24. Power cable from DC power supplies to device must not be longer than 3m. 

Observe the polarity, connect positive (+) of  DC power supplies to V+ and negative (-) end to V- screw terminal block.  ADA-7040 has

the protection from opposite connection power supply. If after power, on the front panel is not lit green LED PWR, check the power

connection (polarity).

4. CONFIGURATION

The operating mode of the ADA-7040 converter is set by the use 6-position SW1 switch. This switch is located near the Fibre-Optic

connectors (see Fig.1). To set the SW1 should remove the terminal cover and using small, flat screwdriver make correct setting.

4.1. SETTING OF OPERATING MODE

All available operating modes are shows in table below. 

If there are any additional questions, please contact with technical support: suppor@cel-mar.pl or on the phone: +48 41 362-12-46.

Table 1. RS422 or RS485 operating mode.

SW1-1 SW1-2 SW1-3 SW1-4 SW1-5 SW1-6

Description

Operating mode

OFF

OFF

OFF

OFF

OFF

OFF

RS-422 bus

4-wire RS422 network. 

Full duplex or half duplex

transmission.

ON

ON

ON

ON

ON

ON

RS-485 bus, 

automatic data flow control

 2-wire and 4-wire RS485 network.

Full duplex or half duplex

transmission.

4.2. DEFAULT SETTING

The ADA-7040 converter is being set in RS485 mode during production as in the table below.

Table 2.

SW1-1 SW1-2 SW1-3 SW1-4 SW1-5

SW1-6

ON

ON

ON

ON

ON

ON

5. ACTIVATION

Converter can be powered after proper connection according to steps above.

If   connection   was   made   properly   green   LED   PWR   on   front   panel   of   converter   should   light,   if   not   check   polarization   of   power

connection.  During proper data transmission through converter  the LEDs Tx and Rx should blink.

5.1.  LEDS DESCRIPTION

LED

Description

PWR Signalization of Power Supply
RX

Signalization of data receiving by the ADA-7040 from RS485 / RS422 port

TX

Signalization of data transmission from the ADA-7040 through RS485/ RS422 port

ATTENTION !!!

AT BAUD RATE OVER 38.400 BPS, THE LEDS WILL LIGHT WEAKLY DURING DATA TRANSMISSION.

7

ADA-7040

Multimode the 
optical fibers, 
types:
50/125um,  
62,5/125 um,  
100/140um, 
200umHCS,  
plastic POF/1mm,

Power Supply

FO

connector

RS422 interface 

device

RS422

connector

TX+

TX-

RX+

RX-

Rt

TX

RX

Rt

RX+

RX-

GND

TX+

TX-

Vss+

Vss-

V -

V +

RS422

connector

ADA-7040

GND

Rt

RX+

RX-

GND

TX+

TX-

Vss+

Vss-

V -

V +

RS422

connector

ADA-7040

RS422

connector

TX+

TX-

RX+

RX-

Rt

GND

TX

RX

Power Supply

FO

connector

RS422 interface 

device

Summary of Contents for ADA-7040

Page 1: ...User manual ADA 7040 Multimode Fibre Optic to RS 485 RS 422 Converter 1 io_ada 7040_v3 24_en ADA 7040 Copyright 2001 2017 CEL MAR sp j...

Page 2: ...N 5 3 INSTALLATION 5 3 1 ASSEMBLING 5 3 2 CONNECTION TO RS485 RS422 NETWORK 5 3 2 1 CONNECTION TO 4 WIRE RS422 NETWORK 5 3 2 2 CONNECTION TO 4 WIRE RS485 NETWORK 6 3 2 3 CONNECTION TO 2 WIRE RS485 NET...

Page 3: ...and the like Complete disable from the supply network is only after disconnecting the power supply circuit voltage Do not carry out the assembly or dis assembly of the device if it is enabled This may...

Page 4: ...d resistance to interference on the transmission bus The fibre connection is implemented by a line consisting of two fibres one fiber for the TX signal and one for RX signal Using two this type conver...

Page 5: ...converter from power circuit device that generates large impulse interference such as transmitters contactors 3 1 ASSEMBLING The ADA 7040 converter case is adapted to assembly on TS 35 DIN35 rail To i...

Page 6: ...3 4 5 Two resistors Rt 120W are supplied with ADA 7040 converter free of charge 3 3 CONNECTION FIBRE OPTIC BUS The multimode Fibre Optic with connectors type ST SC or SMA connect into their correspond...

Page 7: ...FF RS 422 bus 4 wire RS422 network Full duplex or half duplex transmission ON ON ON ON ON ON RS 485 bus automatic data flow control 2 wire and 4 wire RS485 network Full duplex or half duplex transmiss...

Page 8: ...mm optical power budget Tx Rx 9 6 dB up to 2500m for fibre type 62 5 125 mm optical power budget Tx Rx 15 dB up to 2000m for fibre type 100 140 mm optical power budget Tx Rx 15 dB up to 1500m for fib...

Page 9: ...d PN EN 55022 Safety requiring According to the PN EN60950 norm Environment Commercial and light industrial Environmental Parameters Operating temperature 30 C 60 C Humidity 5 95 non condensing Storag...

Page 10: ...10 ADA 7040...

Page 11: ...11 ADA 7040...

Page 12: ...transmission converters with interface RS232 RS485 RS422 USB Current Loop Fibre Optic Converters and Ethernet or Wi Fi Please contact us to tell how you like our products and how we can satisfy you p...

Reviews: