Fig. 6. Example connection of ADA-7040 converters by the use of Fibre-Optic line.
3.4. POWER SUPPLY CONNECTION
The power supply to the ADA-7040 converter should be DC (regulated) from 10 V= to 30V=. Nominal power is typically 2W, e.g. ZS-
12/250 or DR-15-24. Power cable from DC power supplies to device must not be longer than 3m.
Observe the polarity, connect positive (+) of DC power supplies to V+ and negative (-) end to V- screw terminal block. ADA-7040 has
the protection from opposite connection power supply. If after power, on the front panel is not lit green LED PWR, check the power
connection (polarity).
4. CONFIGURATION
The operating mode of the ADA-7040 converter is set by the use 6-position SW1 switch. This switch is located near the Fibre-Optic
connectors (see Fig.1). To set the SW1 should remove the terminal cover and using small, flat screwdriver make correct setting.
4.1. SETTING OF OPERATING MODE
All available operating modes are shows in table below.
If there are any additional questions, please contact with technical support: suppor@cel-mar.pl or on the phone: +48 41 362-12-46.
Table 1. RS422 or RS485 operating mode.
SW1-1 SW1-2 SW1-3 SW1-4 SW1-5 SW1-6
Description
Operating mode
OFF
OFF
OFF
OFF
OFF
OFF
RS-422 bus
4-wire RS422 network.
Full duplex or half duplex
transmission.
ON
ON
ON
ON
ON
ON
RS-485 bus,
automatic data flow control
2-wire and 4-wire RS485 network.
Full duplex or half duplex
transmission.
4.2. DEFAULT SETTING
The ADA-7040 converter is being set in RS485 mode during production as in the table below.
Table 2.
SW1-1 SW1-2 SW1-3 SW1-4 SW1-5
SW1-6
ON
ON
ON
ON
ON
ON
5. ACTIVATION
Converter can be powered after proper connection according to steps above.
If connection was made properly green LED PWR on front panel of converter should light, if not check polarization of power
connection. During proper data transmission through converter the LEDs Tx and Rx should blink.
5.1. LEDS DESCRIPTION
LED
Description
PWR Signalization of Power Supply
RX
Signalization of data receiving by the ADA-7040 from RS485 / RS422 port
TX
Signalization of data transmission from the ADA-7040 through RS485/ RS422 port
ATTENTION !!!
AT BAUD RATE OVER 38.400 BPS, THE LEDS WILL LIGHT WEAKLY DURING DATA TRANSMISSION.
7
ADA-7040
Multimode the
optical fibers,
types:
50/125um,
62,5/125 um,
100/140um,
200umHCS,
plastic POF/1mm,
Power Supply
FO
connector
RS422 interface
device
RS422
connector
TX+
TX-
RX+
RX-
Rt
TX
RX
Rt
RX+
RX-
GND
TX+
TX-
Vss+
Vss-
V -
V +
RS422
connector
ADA-7040
GND
Rt
RX+
RX-
GND
TX+
TX-
Vss+
Vss-
V -
V +
RS422
connector
ADA-7040
RS422
connector
TX+
TX-
RX+
RX-
Rt
GND
TX
RX
Power Supply
FO
connector
RS422 interface
device