-9-
ES-10
Field Installation Manual
Electrical Data Sheet
Model ES-10,
ES-10
(E)
Phase Configuration
Three Phase 120/208V AC
Maximum Line Voltage
208V AC
Maximum Power
7.8 kVar
Monitoring
Power Factor, Voltage, Current , Power, ON status
Accuracy
0.16 kVar each phase
Frequency 60Hz
Protection
Capacitor Inbuilt Protection P2, External Circuit Breaker/Fuse.
Equipment Protection
Internal design has adequate clearance and creepage distance
against line transients. MOVs not required.
Circuit breaker Required
30 Amp 3 pole
Low Losses
0.5 Watt each step
Human Protection
All High voltage shielded from contact.
Operating temperature range
40
o
C Ambient
Dimensions(L X H X D)
16” X 12” X 5” ( 400 x 300 x 120 mm) Metal Enclosure Type 1
Operating Life
Switching tested up to 25,000 times, 6,000 as per UL
Wire Gauge & Rating
10 AWG Str for Power, 22 AWG Str for CT
Unit Weight
10 kg (22 Pounds)
Summary of Contents for ES-10