ES-11

Field Installation Manual

Connection Type # 1

Use this instruction

If 63 Amp circuit breaker is available in customer Main Breaker Panel.

ES-11 is designed for use with Main Breaker Panel Single Phase 120/240V AC
up to 400 Ampere.

ES-11 unit should be mounted with four appropriate sized fasteners before connect to
Main Breaker Panel.

1.1 Power Connections

1.11 Remove the Panel cover of ES-11 exposing internal connections.

1.12 Locate Earth Terminal in ES-11, connect the earth wire to ES-11 Earth Terminal. Connect the other

side of earth wire to main breaker panel ground rod. Ensure all mechanical connections are secure
and making full contact.

1.13 Locate existing 2 Pole 63 Amp Circuit Breaker in the Main Breaker Panel.

(a) Connect the wire L1 to Phase 1 of 63 Amp circuit breaker.

(b) Connect the wire L2 to Phase 2 of 63 Amp circuit breaker.

1.14 Qualified Representative must inspect size of cable 4 AWG.

1.15 Connect power cables to T1 Terminal Block of ES-11.

1.2 Current Sensor Connections

1.21 Open one side of split CT (Current Sensor). Clip the CT on the wire L1 before main Circuit Breaker

as shown in the (fig-1) Page-6.

1.22 Locate terminal block T2 (S1-S2) in ES-11.

1.23 Qualified Representative line side of Main Panel should connect the wires from external CT to

T2 (S1-S2), preferably twisted.

1.24 Firmly secure current sensor to line side (L1) of main circuit breaker.

Summary of Contents for ES-11

Page 1: ..._______________________ 1 ES 11 Field Installation Manual INDEX Important Instructions 2 Product Specifications 3 Unpacking Mounting 4 Connection Type 1 5 Connection Diagram 6 Connection Type 2 7 Connection Type 3 8 Electrical Data Sheet 9 Recommended Part List 10 ...

Page 2: ...nstallation and all components of the installation must be UL listed UL approved and as per NEC code WARNING Celec manufacture components parts that can be used in a wide variety of industrial commercial applications The selection and application of Celec products remains the responsibility of the equipment designer or end user Celec accepts no responsibility for how its products may be incorporat...

Page 3: ... Amp per phase Maximum kVar 11 94 Maximum Ambient Temperature 400 C Enclosure Type 1 Connection Terminal Connection Type Size Wire Type Temperature Torque N m Lb in T1 Power Circuit 4 AWG Str CU 60 75 C 2 5 22 T2 CT Circuit 22 AWG Str Sol CU 60 75 C 0 5 7 Earthing Terminals Bonding Circuit 8 AWG Str Sol CU 60 75 C 8 5 75 Specified as per UL Nominal Current in CT Circuit is less then 100 mA May use...

Page 4: ... given for support during transportation 4 Do not use ES 11 in case of any Breakage or loose connections or Oil Spill inside MOUNTING CAUTION Indoor Use Only Type 1 Enclosure 1 Choose the dry and Clean Wall to Install the ES 11 taking care conduit connections from Bottom side Enclosure Size is 400 x 500 x 120 mm and weight 13kg 29 Pounds 2 Premark the Mounting holes on wall or structure 3 Make a D...

Page 5: ...h wire to main breaker panel ground rod Ensure all mechanical connections are secure and making full contact 1 13 Locate existing 2 Pole 63 Amp Circuit Breaker in the Main Breaker Panel a Connect the wire L1 to Phase 1 of 63 Amp circuit breaker b Connect the wire L2 to Phase 2 of 63 Amp circuit breaker 1 14 Qualified Representative must inspect size of cable 4 AWG 1 15 Connect power cables to T1 T...

Page 6: ...______________________________________________________________________________________ 6 ...

Page 7: ...lable ES 11 unit is designed for use with Customer Main Breaker Panel Single Phase 120 240V AC up to 400 Amp ES 11 units should be mounted with four appropriate sized fasteners before connect to Main Breaker Panel 1 Remove Main Panel covers exposing internal wiring and breakers 2 Remove existing 2 Pole breaker blanks and install new 2 Pole 63 Amp circuit Breakers 3 For rest of connection follow th...

Page 8: ... Circuit Breaker for connection of ES 11 to Customer Main Breaker Panel 1 Install new 63 Amp Blade Fused disconnect or External Circuit Breaker switch to wall or existing backboard Qualified Representative should note if codes allow for direct connection to bus bars in main breaker panel or requires installation of an additional sub panel 2 Wire in rigid conduit between customer main breaker panel...

Page 9: ...tection Capacitor Inbuilt Protection P2 Equipment Protection Internal design has adequate clearance and creepage distance against line transients MOVs not required Circuit breaker Required 63 Amp 2 pole Low Losses 0 5 Watt each step Human Protection All High voltage shielded from contact Operating temperature range 40o C Ambient Dimensions L X H X D 12 X 20 X 5 400 x 500 x 120 mm Metal Enclosure T...

Page 10: ...s required CT Current Sensor Megnelab SCT 0750 050 1 Dowel Plug Size M8 Any 4 Screw 50 mm Size M8 Any 4 1 2 Conduit Connector Any 8 1 2 Tube Conduit Any As required All the Parts used in installation must be UL recognized or UL listed NOTE Installation of material and workmanship at the customer s Main Breaker Panel shall be the responsibility of the qualified Electrician in accordance with NEC An...

Reviews: