background image

Page 10 | 1-855-235-5271

CX

 040418

Locate the desired installation location (no lower than 18 inches from the ceiling).  Using 

a stud finder, locate the studs on either side of the center point, and mark them with 

vertical lines.* Using a level and a pencil, mark a horizontal line on the wall between the 

two studs, no less than 11/2 inches and no more than 18 inches from the ceiling. 

* For the cx8800, special consideration needs to be used when selecting the installation 

location. The system is wider than the 16 inches at which wall studs are typically spaced, 

and will require the removal of at least one stud.

 

Using a ruler or measuring tape, measure vertically down 13.5 inches for the cx2200, 20 

inches down for the cx3300/cx4400, and 22.5 inches for the cx8800. Mark another hori-

zontal line parallel to the first one. 

Using a saw, cut along the uppermost horizontal line until your saw reaches the stud.  

Turn the saw around, inserting it into the cut you have just made, and cut toward the  

opposite stud so that you have a clean horizontal cut between the two studs.  Be careful 

not to cut into the studs themselves.*

* For the cx8800, cut out your drywall first and cut through your studs when you have a clear 

understanding what is inside the wall. 

 

Now make the second horizontal cut from stud to stud on the line below the first cut. 

Once the horizontal lines have been cut, make vertical cuts using the inside edge of the 

studs as a guide. Once you have made both vertical cuts, you should have a rectangular 

hole in the sheetrock.  Now make the same hole on the other side of the wall.  Since you 

already have one hole, this is an easy process. Using a nail, mark all four corners of the 

first hole by making nail holes through the sheetrock. Then, on the other side of the wall, 

connect the holes with a pencil mark and cut.

Sheetrock alone cannot support the weight of a cooling system.  Therefore, it is  

necessary to frame the hole that you have just cut with upper and lower supports. These 

supports also provide solid material for the mounting bracket screws.

Using two 2x4s at 14.5 inches in length and eight 6d nails, secure the upper and lower 

supports to the right and left studs, just inside the sheetrock. Make sure that the internal 

height remains the same so that the system will fit snugly through the framed cut-out.*

* For the cx8800, it is recommended that the entire opening be framed. This system is heavy 

and the sturdier the frame, the better.

PREPARING THE INSTALLATION LOCATION

Minimum Tools Needed:

 

Hammer

Saw

Screwdriver

Level

Summary of Contents for cx2200

Page 1: ...CX SERIES OWNER S MANUAL cx2200 cx3300 cx4400 cx8800...

Page 2: ...not responsible for printing or clerical errors CellarCool reserves the right to make corrections or improvements to the information provided and to the related hardware at any time without notice Vi...

Page 3: ...tallation Airflow Control 9 Preparing the Installation Location 10 Preparing the Unit for Installation 11 Installing the System 11 Drain Line 13 System Operation 14 Controller Functions 15 Wiring Sche...

Page 4: ...ool cooling unit is a specialized refrigeration unit designed for one purpose only to maintain the optimal temperature and humidity levels conducive to the proper storage and aging of fine wines It is...

Page 5: ...of the cellar over time by cycling cooler air throughout Test the unit prior to installation 5 You are required to install a drain line to remove condensation from the unit 6 The CellarCool unit is in...

Page 6: ...utlet Power surges and spikes can damage sensitive electrical equipment CellarCool recommends plugging the unit into a surge protector or power conditioner in order to protect your system As outlined...

Page 7: ...5 CX SERIES QUICK REFERENCE GUIDE Front Side View Rear Side View Controller Power cord front location standard ON OFF switch for 4400 8800 models only Power cord rear location optional Air sensor Rear...

Page 8: ...s parts and labor 5 years compressor Sizing the Unit to the Room The specification chart will provide information on the unit s cooling capacity There are circumstances in which a cellar design may re...

Page 9: ...ly use CellarCool products It is vital that all walls and ceilings be insulated to keep the cellar temperature as consistent as possible during the summer and winter months Standard fiberglass or rigi...

Page 10: ...rtion of the unit NOTE High humidity significantly increases the heat load on the cooling system Any break in the vapor barriers a cut a nail hole overlapping etc will cause a moisture leak and must b...

Page 11: ...will best suit your installation NOTE Do not cover both of the openings on the same side of the unit for any reason This will cause cooling issues and premature failure NOTE Do not cover both of the...

Page 12: ...rough your studs when you have a clear understanding what is inside the wall Now make the second horizontal cut from stud to stud on the line below the first cut Once the horizontal lines have been cu...

Page 13: ...ellar Note If you use decorative moulding it should be attached to the walls and never to the cooling unit itself The moulding itself should be removable incase the unit needs servicing Applying Insul...

Page 14: ...n each side of the side of the unit you will notice 6 indents these mark two different installation depths Select one of the two mounting depths and attach each mounting bracket to the unit with the s...

Page 15: ...s important that the drain line tube be properly connected and used to prevent leakage and other problems associated with excess condensation Failure to use the condensation drain line tube will void...

Page 16: ...has reached the setpoint to allow the pressure in the refrigeration unit to equalize prior to starting the compressor Anti Frost Cycle defrost After two hours of compressor operation the controller w...

Page 17: ...utton once more Use the UP and DOWN ARROW buttons in order to change the value until the desired setpoint is reached Hold the set button for approximately 5 seconds to enter the CPSM Customer Preferen...

Page 18: ...snowflake symbol will not be lit 2 Add heat to the room until the wine reaches the desired temperature Press and hold the SET button for approximately 5 seconds to enter the CPSM menu Use the DOWN AR...

Page 19: ...www cellarcool com Page 17 CX SERIES cx2200 cx3300 CONTROLLER WIRING SCHEMATIC Cond Fan Compressor Cond Fan Evap Fan Evap Fan...

Page 20: ...Page 18 1 855 235 5271 CX 040418 cx4400 CONTROLLER WIRING SCHEMATIC Cond Fan Compressor Cond Fan Evap Fan Evap Fan...

Page 21: ...www cellarcool com Page 19 CX SERIES cx8800 CONTROLLER WIRING SCHEMATIC Cond Fan Compressor Cond Fan Evap Fan Evap Fan...

Page 22: ...Page 20 1 855 235 5271 CX 040418 NOTES...

Page 23: ...ine voltage is incorrect rating for unit Check line voltage to make sure there is 110V 120V Room at setpoint Lower setpoint Thermostat not calling for cooling Lower setpoint Faulty thermostat or wirin...

Page 24: ...Solution Lack of airflow heat exhaust outer room Make sure fan is unobstructed clean evaporator if necessary The unit is undersized for the room Purchase correctly sized unit Evaporator fan runs but...

Page 25: ...USING INTERIOR DRAIN LINE Insert supplied drain line brush from this end Drop pan tab into drip tray through access door ACCESS DOOR CX2200 ACCESS DOOR CX3300 4400 8800 ACCESS DOOR SCREWS REAR OF UNIT...

Page 26: ...arCool Customer Service 1738 E Alpine Ave Stockton CA 95205 www cellarcool com Email support cellarcool com Tech Support Customer Service 1 800 343 9463 Sales Sizing Assistance 1 855 235 5271 Fax 209...

Page 27: ...d in the event the Product is not repairable in the field cover normal ground freight charges within the continental United States for the repair or replacement of the Product B Five 5 Year Compressor...

Page 28: ...arCool Owner s Manual and thereafter the End User must follow the required installation use and maintenance procedures set forth by CellarCool in CellarCool s Owner s Manual The Owner s Manual is ship...

Page 29: ...t 1738 East Alpine Avenue Stockton California 95205 8 Miscellaneous Terms and Conditions A Return Policy All return inquiries must be made within thirty 30 calendar days of the original purchase of a...

Page 30: ...343 9463 or please send a letter via U S Mail to Customer Service CellarCool Corporation 1738 E Alpine Ave Stockton CA 95205 Email support cellarcool com Web www cellarcool com B Technical Assistance...

Page 31: ...CellarCool 1738 E Alpine Ave Stockton CA 95205 1 800 343 9463 www cellarcool com...

Reviews:

Related manuals for cx2200