background image

www.cellarcool.com | Page 21

 CX SERIES

TROUBLESHOOTING GUIDE

Unit has ice forming on the evaporator 

Possible cause

Solution

Evaporator coil is dirty

Clean coil with a vacuum. If coil is very dirty, use a spray bottle with a 
small amount of liquid dish detergent. Spray coil, let set for 5 minutes, 
then flush with fresh water.

Something is blocking the supply and/or return air

Remove blockage

Evaporator fan is not turning on

Call installing technician to troubleshoot

The temperature of the room to which the unit is exhausting has 
dropped below 50°F

Raise the temperature of the exhaust room

Unit has not gone through an Anti-Frost Cycle

Check for ice in the depth of the coil. Melt with blow drier until coil is 
warm to the touch. Soak up water with a towel.

Unit continues to ice

Observe ice formation pattern. If only part way up the coil face, unit 
could be low on refrigerant. If all the way up, the coil may be dirty or 
airflow is blocked.

Unit does not run/power up 

Possible cause

Solution

Unit is not plugged in

Make sure the unit is plugged into an outlet

No power to outlet

Contact an electrician

Line voltage is incorrect rating for unit

Check line voltage to make sure there is 110V-120V

Room at setpoint

Lower setpoint

Thermostat not calling for cooling

Lower setpoint

Faulty thermostat or wiring

Call Customer Service at 1-800-343-9463

Cellar temperature is too warm

Possible cause

Solution

Temperature of the room unit is exhausting to has exceeded 85°F

Intake temperature needs to drop below 85°F

Unit is undersized for the cellar

Order correctly sized unit

Something is blocking the supply and/or return air on evaporator or 
condenser side of the unit

Remove airflow obstruction

Unit is mounted too low in the cellar

Relocate unit so the distance from the ceiling and top of the unit is no 
more than 18”

One or more of the fans is not turning on

Call Customer Service at 1-800-343-9463

Compressor is not turning on

Call Customer Service at 1-800-343-9463

Compressor keeps cycling on overload

Make sure all fans are working and there is no airflow obstruction

Poor seal around door

Make sure there are no air gaps around the door. If door seal is 
damaged, replace it.

Controller set too high

Lower the setpoint

Evaporator coil is frosted or iced up

Observe ice formation pattern. If only part way up the coil face, unit could 
be low on refrigerant. If so, call Customer Service at 1-800-343-9463.

Summary of Contents for cx2200

Page 1: ...CX SERIES OWNER S MANUAL cx2200 cx3300 cx4400 cx8800...

Page 2: ...not responsible for printing or clerical errors CellarCool reserves the right to make corrections or improvements to the information provided and to the related hardware at any time without notice Vi...

Page 3: ...tallation Airflow Control 9 Preparing the Installation Location 10 Preparing the Unit for Installation 11 Installing the System 11 Drain Line 13 System Operation 14 Controller Functions 15 Wiring Sche...

Page 4: ...ool cooling unit is a specialized refrigeration unit designed for one purpose only to maintain the optimal temperature and humidity levels conducive to the proper storage and aging of fine wines It is...

Page 5: ...of the cellar over time by cycling cooler air throughout Test the unit prior to installation 5 You are required to install a drain line to remove condensation from the unit 6 The CellarCool unit is in...

Page 6: ...utlet Power surges and spikes can damage sensitive electrical equipment CellarCool recommends plugging the unit into a surge protector or power conditioner in order to protect your system As outlined...

Page 7: ...5 CX SERIES QUICK REFERENCE GUIDE Front Side View Rear Side View Controller Power cord front location standard ON OFF switch for 4400 8800 models only Power cord rear location optional Air sensor Rear...

Page 8: ...s parts and labor 5 years compressor Sizing the Unit to the Room The specification chart will provide information on the unit s cooling capacity There are circumstances in which a cellar design may re...

Page 9: ...ly use CellarCool products It is vital that all walls and ceilings be insulated to keep the cellar temperature as consistent as possible during the summer and winter months Standard fiberglass or rigi...

Page 10: ...rtion of the unit NOTE High humidity significantly increases the heat load on the cooling system Any break in the vapor barriers a cut a nail hole overlapping etc will cause a moisture leak and must b...

Page 11: ...will best suit your installation NOTE Do not cover both of the openings on the same side of the unit for any reason This will cause cooling issues and premature failure NOTE Do not cover both of the...

Page 12: ...rough your studs when you have a clear understanding what is inside the wall Now make the second horizontal cut from stud to stud on the line below the first cut Once the horizontal lines have been cu...

Page 13: ...ellar Note If you use decorative moulding it should be attached to the walls and never to the cooling unit itself The moulding itself should be removable incase the unit needs servicing Applying Insul...

Page 14: ...n each side of the side of the unit you will notice 6 indents these mark two different installation depths Select one of the two mounting depths and attach each mounting bracket to the unit with the s...

Page 15: ...s important that the drain line tube be properly connected and used to prevent leakage and other problems associated with excess condensation Failure to use the condensation drain line tube will void...

Page 16: ...has reached the setpoint to allow the pressure in the refrigeration unit to equalize prior to starting the compressor Anti Frost Cycle defrost After two hours of compressor operation the controller w...

Page 17: ...utton once more Use the UP and DOWN ARROW buttons in order to change the value until the desired setpoint is reached Hold the set button for approximately 5 seconds to enter the CPSM Customer Preferen...

Page 18: ...snowflake symbol will not be lit 2 Add heat to the room until the wine reaches the desired temperature Press and hold the SET button for approximately 5 seconds to enter the CPSM menu Use the DOWN AR...

Page 19: ...www cellarcool com Page 17 CX SERIES cx2200 cx3300 CONTROLLER WIRING SCHEMATIC Cond Fan Compressor Cond Fan Evap Fan Evap Fan...

Page 20: ...Page 18 1 855 235 5271 CX 040418 cx4400 CONTROLLER WIRING SCHEMATIC Cond Fan Compressor Cond Fan Evap Fan Evap Fan...

Page 21: ...www cellarcool com Page 19 CX SERIES cx8800 CONTROLLER WIRING SCHEMATIC Cond Fan Compressor Cond Fan Evap Fan Evap Fan...

Page 22: ...Page 20 1 855 235 5271 CX 040418 NOTES...

Page 23: ...ine voltage is incorrect rating for unit Check line voltage to make sure there is 110V 120V Room at setpoint Lower setpoint Thermostat not calling for cooling Lower setpoint Faulty thermostat or wirin...

Page 24: ...Solution Lack of airflow heat exhaust outer room Make sure fan is unobstructed clean evaporator if necessary The unit is undersized for the room Purchase correctly sized unit Evaporator fan runs but...

Page 25: ...USING INTERIOR DRAIN LINE Insert supplied drain line brush from this end Drop pan tab into drip tray through access door ACCESS DOOR CX2200 ACCESS DOOR CX3300 4400 8800 ACCESS DOOR SCREWS REAR OF UNIT...

Page 26: ...arCool Customer Service 1738 E Alpine Ave Stockton CA 95205 www cellarcool com Email support cellarcool com Tech Support Customer Service 1 800 343 9463 Sales Sizing Assistance 1 855 235 5271 Fax 209...

Page 27: ...d in the event the Product is not repairable in the field cover normal ground freight charges within the continental United States for the repair or replacement of the Product B Five 5 Year Compressor...

Page 28: ...arCool Owner s Manual and thereafter the End User must follow the required installation use and maintenance procedures set forth by CellarCool in CellarCool s Owner s Manual The Owner s Manual is ship...

Page 29: ...t 1738 East Alpine Avenue Stockton California 95205 8 Miscellaneous Terms and Conditions A Return Policy All return inquiries must be made within thirty 30 calendar days of the original purchase of a...

Page 30: ...343 9463 or please send a letter via U S Mail to Customer Service CellarCool Corporation 1738 E Alpine Ave Stockton CA 95205 Email support cellarcool com Web www cellarcool com B Technical Assistance...

Page 31: ...CellarCool 1738 E Alpine Ave Stockton CA 95205 1 800 343 9463 www cellarcool com...

Reviews: