28
V9.20
Up and Down Buttons
To view the “
High Temp
” recorded by the
cooling unit, press the “Up” button once.
To view the “
Low Temp
” recorded by the
cooling unit, press the “Down” button once.
To
reset
the “High Temp” or “Low Temp”,
press the “Set” button for three seconds
while “Hi” or “Lo” is displayed. “RST” will
blink three times to indicate confirmation.
Set Button
The cooling unit is factory preset with a
Minimum Set Point of 58°F and a
Temperature Differential of 4°F. This means
that the cooling unit will turn on when the
display rises above 62°F (58°F + 4°F), and
turn off when the display falls below 58°F.
In this example, the average temperature
inside the cellar will be 60°F.
To view the Minimum Set Point, press the
“Set” button for one second.
To change the Minimum Set Point,
Press the “Set” button for three
seconds until °F” blinks
Press “Up” or “Down” button
Press “Set” button to confirm
The “Set” temperature will blink three times
to indicate confirmation
The recommended Minimum Set Point
range is 53 - 60°F. To change the
Temperature Differential, see “Advanced
Operation” later in this chapter.