The left-hand corner might then show "CUTOUT I-DATA". This means that a transformer factor must be
entered. Enter password "1.5" and go to SETP/I:
When picture "SETP/I" appears, key <F5> followed by the transformer factor.
The transformer factor is determined by:
Transformer factor =
(input current corresponding to 20 mA output on the current converter instrument)
Full load current of motor
The current converter instrument must have a range of input current there go higher than the full load
motor current, so an over load can be measured. A range there goes up to 25% higher will be very
suitable.
Example: When using an instrument transformer where the primary current is 200 A and a motor with a
rated current of 180 A
The transformer factor will make =
200
180
= 1,11
When the factor has been entered, push <ENTER> to update and then <
ee
> to return to the initial picture.
The text "CUTOUT I-DATA" is removed from the initial picture by pushing the <F6> (Clear alarm). In
principle the compressor is now ready for start, but in most cases the set points are to be altered, and the type
of duty has to be indicated; see following section.