TYPES OF DUTY
CELLmatic offers the possibility of 4 types of duty:
1. MASTER OPERATION
2. SLAVE OPERATION
3. REMOTE CONTROL OPERATION
4. MANUAL OPERATION
F5 is activated from the initial picture and you go to SETUP 1
01-01-94 17:25:35
SETUP 1/
F6 CLA :Select type of operation (F5):
F5 OPERATION:1=Master 2=Slave 3=Manual
F4 :4=Remote w. ext. setp (remot4)
F3 I/O :5=Remote w. own setp (remot5)
F2 SETUP 2 :
F1 STOP : STOP
Note:
In the SETUP 1 picture the whole text field is attached to the F5 key "OPERATION". The type of
duty is selected by entering <F5> followed by a number from 1 to 5 dependent on the required type of
duty.
1. Master operation
If master operation is selected the message "MASTER" will appear on the bottom of the report line.
This type of duty can be selected if the compressor is not connected with other compressors (also called "stand
alone"), and you want it to run according to its own set point.
The master compressor is able to control one or more subsequent compressors (slaves). The slaves will all be
controlled by the setpoint of the master compressor.
For master operation the following conditions have to be fulfilled before the compressor will start:
-Restart period expired
- Call for capacity, that is P
SUCTION
[°C] > (P
SUCT-SETP
+P
SUCT-START
)
T
BRINE
> (T
BRINE-SETP
+T
BRINE-START
)
- Reset of possible cutout <
CLA
>
- Slide valve at its minimum (
C
ABS
< 15%)
- Oil pump is started and the oil pressure are greater than (Oildiff. Alarm)
Under setp E a choice can be made: control in accordance with the suction pressure or the brine temperature,
see description of setpoints.
If the compressor has started it will stay in its minimum until the motor is in delta. After this the capacity will
be increased until it has reached its "minimum capacity" (Setp. C). The internal volume ratio of the compressor
will now adjust to the volume ratio of the plant (Vi), and the capacity is controlled by the suction pressure.
This is done by sending electrical signals to two solenoid valves mounted on the oil manifold of the
compressor.
If the slide valve or the slide stop is adjusted upwards, a "C+" or a "V+" is shown in the display. In case of a
downward adjusting a "K-" or a "V-" is shown. If the suction pressure is within the dead zone there will be no
regulation of capacity. If the suction pressure lies within the dead zone, capacity will not be regulated and
"CN" will be shown on the display.